Edge [ii] Controller Operation Manual
SECTION 4: DIAGNOSTICS
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
80
of
196
4.3.2 Analog Outputs
The Analog
Outputs
screen displays the current values of the various analog outputs and
allows you to manually adjust their values.
1. Go to:
Main Menu
→
Diagnostics
→
Analog Outputs and Relays
→
Analog Outputs
.
DEFAULT MODE
MANUAL MODE
Figure 4.3.2: Analog Outputs and Relays: Analog Outputs Screen
2. In Default mode, this screen is grey and displays the current value (read-only) of all analog
outputs.
3. If you press the
Manual
button
, the unit’s fire rate is reduced to zero and the sliders turn
green. You can now manually adjust the position of one or more of the outputs and verify
the behavior of the selected output(s). You can return all sliders to 0.00 by pressing the
Zero
button.
4. To put this screen back in Default mode, press the
Manual
button again.
4.4 Subsystems
The
Subsystems
screens allows you to test the units Air/Fuel Valve, Blower and Ignition.
NOTE:
You can navigate from one
Subsystem
screen to the next in round-robin fashion using
the
Page Left
and
Page Right
icons on each screen.
1. Go to
: Main Menu
→
Diagnostics
→
Subsystems
.
Figure 4.4: Diagnostics: Subsystems Screen
2. Press on the component you want to test.