Edge [ii] Controller Operation Manual
SECTION 2: EZ SETUP
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
27
of
196
2. If you chose
Constant Setpoint
in
Step 1, the
Other Heating Constant Setpoint
screen
appears. Specify the
Unit Other Setpoint
. Pressing
Next
takes you to the
Select BAS
Mode
Figure 2.2.3-3: Standalone
– Other: Other Heating Constant Setpoint Screen
3. If you chose
Remote Setpoint
in step 1, the
Select Remote Setpoint Type
screen
appears. Choose how the unit will access the setpoint, then press
Next
.
Figure 2.2.3-4: Standalone
– Other: Select Remote Setpoint Type Screens
A. If you chose either
4-20mA
or
0-20mA
the
Other Analog Input
screen appears.
Configure the following parameters:
Figure 2.2.3-5: Standalone
– Other: Other Analog Input Screen
•
Enter the upper and lower limits of the “other” setpoint in the
Unit Other
Setpt Low Limit
and
Unit Other Setpt High Limit
parameters.
•
Pressing
Next
takes you to the
Select BAS Mode