Edge [ii] Controller Operation Manual
SECTION 6
– ADVANCED SETUP
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
155
of
196
4. For all values of
Name
except
Not Assigned
, configure the remaining parameters for the
input chosen in Step 2:
•
Min & Max Signal Level
: Enter values in the
Min
and
Max Signal Level
parameters.
These two values define the range of the input signal. (Range: 0 to 100).
•
Min & Max Parameter Level
: Enter values in the Min and Max Parameter Level
parameters. These two values define the range to which the analog input signal level
defined in
Min & Max Signal Level
will be linearly mapped. (Range: 0 to 100).
5. Configure the
Rem Spr Ain # Addr
(Remote Spare Analog In X Address, where
X
corresponds to the input chosen in Step 2): Specify the address of the unit from which the
analog input signal is received. (Range: 0 to 16)
6. If needed, repeat Steps 2
– 5 for the other two analog inputs.
6.6 Performance
The
Performance
screen provides access to control and performance parameters for AERtrim,
Temperature and Fire Control functionality. All three
Performance
screens apply only to the
individual unit (they are not part of BST functionality).
Some unit level parameters are not applicable if BST is enabled. In that case, those parameters
are greyed out or hidden. As a result, the screens shown below may include parameters that
don’t appear on the unit you are working on.
The AERtrim option is enabled only on units equipped with a functional O
2
sensor. If O
2
sensor
is not detected or has faulted, the AERtrim button is greyed out.
1. Go to:
Main Menu
→
Advanced Setup
→
Performance
.
Figure 6.6: Advanced Setting: Performance
NOTE:
You can navigate from one
Performance
screen to the next in round-robin fashion using the
Page Left
and
Page Right
icons on each screen.