SECTION 10:
STARTUP, STATUS, FAULT MESSAGES
The Edge Controller displays status messages at various times showing the current state of the
Controller. All status messages are displayed near the top of the touchscreen in
WHITE
text,
just under the current screen’s title.
10.1 FAULT MESSAGES
The Edge Controller displays the following status messages when appropriate. The
#
column
lists the corresponding code returned to Building Automation Systems.
Four types of messages can appear on the Edge Controller’s display screen:
•
Message
: Information about a current event or condition: no intervention required.
•
Warning
: An abnormal event or condition occurred, but the unit continues to operate
normally: no intervention required.
•
Fault
: An abnormal event or condition occurred that caused the unit to shut down. The
unit will restart automatically once the cause of the fault is resolved.
•
Fault, Manual Reset
: An abnormal event or condition occurred that caused the unit to
shut down. A corrective action may be required. Once the cause of the fault is resolved,
the Controller’s
CLEAR
button must be pressed manually to restart the unit.
TABLE 10-1: Edge Controller Fault Messages
#
FAULT MESSAGE
DESCRIPTION
TYPE
0
NO FAULTS
1
Disabled
Indicates the
Enable/Disable
switch is set to
Disabled
. The display also shows the time (AM
or PM) and date that the unit was disabled.
Message
2
Standby
Displayed when ON/OFF switch is in the
ON
position, but there is no demand for heat. The
time and date are also displayed.
Message
3
Demand Delay
Demand Delay is active.
Message
4
Purging
The duration of the purge cycle during startup, in
seconds.
Message
5
Ignition Trial
Displayed during ignition trial startup sequence.
The duration of cycle counts up in seconds.
Message
6
Flame Proven
Displayed after flame has been detected for a
period of 2 seconds. Initially, the flame strength
is shown in %. After 5 seconds has elapsed, the
time and date are shown in place of flame
strength.
Message
7
Warmup
Displayed for 2 minutes during the initial warm-
up only.
Message
8
High Water Temp Switch Open
The High-Water Temperature Limit switch is
open.
Fault, Manual
Reset
9
Low Water Level
The Low Water Cutoff board is indicating low
water level.
Fault, Manual
Reset
10
Low Gas Pressure Fault
The Low Gas Pressure Limit switch is open
Fault, Manual
Reset
11
Gas Pressure Fault
The Gas Pressure Limit switch is not connected
or malfunctioned
Fault, Manual
Reset