Edge [ii] Controller Operation Manual
SECTION 6
– ADVANCED SETUP
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
106
of
196
•
OAR Min Setpoint
: The
minimum
allowable setpoint.
(Range: 20°F to 210°F or
Max Setpoint
, Default = 160°F)
•
Outdoor Rst Setpt
: A read-only display of the current outdoor reset setpoint,
based on the four OAR parameters configured above.
7. If
Unit Application
=
DHW
, choose the
Unit DHW Operating Mode
for the unit,
either Constant
Setpt
or
Remote Setpt
.
Figure 6.2.6-5: Unit Application Configuration, Unit DHW Remote Signal = Network
A. If
Unit DHW Operating Mode
=
Constant Setpt
,
specify the setpoint for DHW
operation in the
Unit DHW Setpoint
parameter. (Range: 80°F to 160°F)
B. If
Unit DHW Operating Mode
=
Remote Setpt
, the following additional
parameters appear:
•
Analog Input Source
: Select the source for the remote setpoint:
Spare
Analog In 1
,
Spare Analog In 2
,
Spare Analog In 3
.
•
Name
: Choose the name of the device to associate with the analog input:
o
Not Assigned
o
Swing V1 Fdbk
o
Blr VSP Fdbk
o
SmartPlate VP
o
Remote Setpt 2
o
Swing V2 Fdbk
o
DHW VSP Fdbk
o
NOx
NOTE:
The
Analog Input Source
and
Name
parameters also appear in Step 8b, below, and in
. Changing them in any one changes them in the others.
•
Unit DHW Remote Signal
: Choose the signal type of the selected device:
o
1-5V
o
Network
o
0-5V
o
BAS