Edge [ii] Controller Operation Manual
SECTION 6
– ADVANCED SETUP
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
144
of
196
6.3.5 SmartPlate Communication
The
SmartPlate Communication
screen provides parameters for configuring communication
between SmartPlate units and a
“Manager” boiler.
NOTE
:
This screen is available only after BST Cascade functionality has been enabled (see the
Unit Mode
parameter in
). If the unit is configured as
a
BST Manager
, the parameters apply to this unit and all BST Client units.
This screen is available only after BST Cascade functionality has been enabled (see Section
6.3.1:
Cascade Configuration
,
Unit Mode
parameter). If the unit is configured as a
BST
Manager
, the parameters apply to this unit and all BST Client units in the cascade.
1. Go to:
Main Menu
→
Advanced Setup
→
BST Cascade
→
SmartPlate Comm
.
Figure 6.3.5: BST Cascade: SmartPlate Communication Screen
2. This screen contains the following parameters:
•
Number of SmartPlates
: Quantity of SmartPlate units in the BST Cascade.
(Range: 0 to 6)
•
SmartPlate Start Address
: The address of the first SmartPlate in the BST
Cascade. (Range: 50 to 54)
•
SmartPlate Setpoint
: The setpoint of the SmartPlate units. (Range: 0 to 140°F)
•
SmartPlate Pmp Unit Addr
: Address of the SmartPlate whose feedback will be
used to control the variable speed DHW pump. (Range: 0 to 255)
•
VP Pump Threshold
: SmartPlate Valve Position threshold, which lowers pump
speed from 10V. (Range: 20% to 70%)
•
Low VP Time
: Amount of time SmartPlate is in VP (Valve Position) Pump Threshold
before reducing DHW pump speed. (Range: 1 to 15 min.)
•
Low VP Pump Voltage
: The voltage to which the pump is reduced to after
SmartPlate units meets
VP Pump Threshold
and
Low VP Time
has expired.
(Range: 2 to 8 V)