Edge [ii] Controller Operation Manual
SECTION 2: EZ SETUP
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
47
of
196
11. The
Swing Boiler Settings
screen appears. Configure the following parameters:
Figure 2.3.2.2.1-14: BST Manager
– SH & DHW: EZ Setup Complete Screen
•
DHW Setup
: Choose one:
o
2 Port Tank
o
4 Port Tank
o
Indirect Tank
•
Default Swing Boiler Load
: Choose one of the following:
o
Swing Default SH
o
Swing Default DHW
•
DHW Pump Unit Address
: Enter the address of the unit containing the DHW
Pump. (Range: 1 to 16)
•
DHW Pump Control Type
: Choose either
Constant On
or
Controlled
.
12. Once all
DHW
parameters have been configured, the
Select BAS Mode
screen appears.
Skip to
2.3.2.2.2
EZ Setup: BST Manager
–
DHW and Other Applications
Complete these instructions only if you chose
both
DHW
and
Other
at the end of Section 2.3.2.
Figure 2.3.2.2.2-1: BST Manager
– DHW & Other: Select Your Boiler Application