Edge [ii] Controller Operation Manual
SECTION 6
– ADVANCED SETUP
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
124
of
196
3. If the unit is configured as a
BST Manager
, the following additional parameters appear:
•
Min & Max Addresses
: The address range of the units in the BST cascade.
(Range: 1 to 16)
•
SSD Temp Format
: Choose either
Points
or
Degrees
.
6.3.3 BST Application Configuration
The BST
Cascade’s Application
Configuration
screen allows you to configure individual
operating parameters that will be transmitted to all BST Client units.
Some parameters below appear in
EZ Setup
(see Section 2). This screen allows you to modify
individual parameters, as needed.
NOTES
:
•
This screen is available only after BST Cascade functionality has been enabled (see the
Unit Mode
parameter in
).
•
If the unit is configured as a
BST Manager
, the parameters apply to this unit and will be
transmitted to all BST Client units. If the unit is configured as a
BST Client
, the parameters
configured on the
BST Manager
will take precedence.
•
If BST Cascade functionality is enabled on a unit, the
1. Go to:
Main Menu
→
Advanced Setup
→
BST Cascade
→
Application Configuration
.
APPLICATION = SH (Space Heating)
APPLICATION = DHW
APPLICATION = OTHER
APPLICATION = SH+DHW-1Vlv
Figure 6.3.3: BST Cascade: Application Configuration
– Example 1
st
Screens