164 • I/O Modules
Process Data Architecture for CANopen
WAGO-I/O-SYSTEM
750
CANopen
lustrate the Input and Output Process Image, which has a total of 6 bytes
mapped into each image.
Input Process Image
Sub-
index
Offset
byte Destination
Remark
0 S
Status
byte
1 -
not
used
2 D0
3 D1
4 D2
n
5 D3
Counter Value
These modules present themselves with 1x6 bytes, so that the object 0x3200
for 6 byte Special Modules, Inputs is used. Therefore for each module one
Subindex is occupied.
Output Process Image
Sub-
index
Offset
byte Destination
Remark
0 C
Control
byte
1 -
not
used
2 D0
3 D1
4 D2
n
5 D3
Counter Setting Value
These modules present themselves with 1x6 bytes, so that the object 0x3300
for 6 byte Special Modules, Outputs is used. Therefore for each module one
Subindex is occupied.
750-404 /000-005
The above Counter Modules have a total of 5 bytes of user data in both the In-
put and Output Process Image (4 bytes of counter data and 1 byte of con-
trol/status). The two counter values are supplied as 16 bits. The following ta-
bles illustrate the Input and Output Process Image, which has a total of 6 bytes
mapped into each image.
Input Process Image
Sub-
index
Offset
byte Destination
Remark
0 S
Status
byte
1 -
not
used
2 D0
3 D1
Counter Value of Counter 1
n
4
D2
Counter Value of Counter 2