The WAGO-I/O-SYSTEM 750
•
37
Power Supply
WAGO-I/O-SYSTEM 750
CANopen
2.7.4 Supplementary power supply regulations
The WAGO-I/O-SYSTEM 750 can also be used in shipbuilding or offshore
and onshore areas of work (e.g. working platforms, loading plants). This is
demonstrated by complying with the standards of influential classification
companies such as Germanischer Lloyd and Lloyds Register.
Filter modules for 24-volt supply are required for the certified operation of the
system.
Item No.
Name
Description
750-626
Supply filter
Filter module for system supply and field supply (24 V,
0 V), i.e. for field bus coupler/controller and bus power
supply (750-613)
750-624
Supply filter
Filter module for the 24 V- field supply
(750-602, 750-601, 750-610)
Therefore, the following power supply concept must be absolutely complied
with.
Fig. 2-21: Power supply concept
g01xx11e
Note
Another potential power terminal 750-601/602/610 must only be used behind
the filter terminal 750-626 if the protective earth conductor is needed on the
lower power contact or if a fuse protection is required.