The WAGO-I/O-SYSTEM 750
•
29
Power Supply
WAGO-I/O-SYSTEM 750
CANopen
2.7 Power Supply
2.7.1 Isolation
Within the fieldbus node, there are three electrically isolated potentials.
•
Operational voltage for the fieldbus interface.
•
Electronics of the couplers/controllers and the bus modules (internal bus).
•
All bus modules have an electrical isolation between the electronics (inter-
nal bus, logic) and the field electronics. Some digital and analog input
modules have each channel electrically isolated, please see catalog.
Fig. 2-10: Isolation
g0xxx01e
Attention
The ground wire connection must be present in each group. In order that all
protective conductor functions are maintained under all circumstances, it is
recommended that a ground wire be connected at the beginning and end of a
potential group. (ring format, please see chapter "2.8.3"). Thus, if a bus mod-
ule comes loose from a composite during servicing, then the protective con-
ductor connection is still guaranteed for all connected field devices.
When using a joint power supply unit for the 24 V system supply and the
24 V field supply, the electrical isolation between the internal bus and the
field level is eliminated for the potential group.