The WAGO-I/O-SYSTEM 750
•
17
Technical Data
WAGO-I/O-SYSTEM 750
CANopen
Range of
application
Required specification
emission of interference
Required specification
immunity to interference
Industrial areas
EN 61000-6-4 (2001)
EN 61000-6-2 (2001)
Residential areas
EN 61000-6-3 (2001)*)
EN 61000-6-1 (2001)
*)
The system meets the requirements on emission of interference in residential areas with
the fieldbus coupler/controller for:
ETHERNET
LonWorks
CANopen
DeviceNet
MODBUS
750-342/-841/-842/-860
750-319/-819
750-337/-837
750-306/-806
750-312/-314/ -315/ -316
750-812/-814/ -815/ -816
With a special permit, the system can also be implemented with other fieldbus cou-
plers/controllers in residential areas (housing, commercial and business areas, small-scale
enterprises). The special permit can be obtained from an authority or inspection office. In
Germany, the Federal Office for Post and Telecommunications and its branch offices
issues the permit.
It is possible to use other field bus couplers/controllers under certain boundary condi-
tions. Please contact WAGO Kontakttechnik GmbH & Co. KG.
Maximum power dissipation of the components
Bus modules
0.8 W / bus terminal (total power dissipation, sys-
tem/field)
Fieldbus coupler/controller
2.0 W / coupler/controller
Warning
The power dissipation of all installed components must not exceed the maxi-
mum conductible power of the housing (cabinet).
When dimensioning the housing, care is to be taken that even under high ex-
ternal temperatures, the temperature inside the housing does not exceed the
permissible ambient temperature of 55 °C.