140 • CANopen
Network
Communication
WAGO-I/O-SYSTEM
750
CANopen
4.3.5.4 Transmit PDO2
The following diagram shows an overview of the relevant objects and their
connection for the PDO transmission of analog inputs.
ENTRY
into
0x6401
MAP
into
TPDO2...4
TRANS
MIT
TPDO2...4
= 1
XOR
CLOSE
IF
TRUE
SINGLE
ANALOG
INPUT
0x6424
0x6425
0x6426
Upper Limit
Lower Limit
Value Difference
0x1A01...3
Default
Mapping
Parameter
0x1801...3
Default
Communication
Parameter
0x6423
Interrupt
Enable
CAN
Transmission
&
AND
0x6427
Negative
Value Difference
0x6428
Positive
Value Difference
Fig. 4-2: PDO transmission of analog input data
g012458x
Index
Object name
Description
See on
page:
0x1801...3
Transmit PDO Communication
Parameter
Communication parameters for the Receive PDOs
0x1A01…3
Transmit PDO Mapping Parameter Mapping parameters for the Transmit PDOs
0x6401
Analogue Input Trigger Selection
Specify the Trigger condition for the 16 bits analog
input data
0x6423
Analogue Input Global Interrupt
Enable
Global release of the transmission of 16 bits analog
input data
0x6424
Analogue Input Interrupt Upper
Limit Integer
Transmission of 16 bits analog input data, if ex-
ceeded the upper limit
0x6425
Analogue Input Interrupt Lower
Limit Integer
Transmission of 16 bits analog input data, if fell
below the lower limit
0x6426
Analogue Input Interrupt Delta
Unsigned
Transmission if the 16 bits input data changed at
least around the delta value
0x6427
Analogue Input Interrupt Negative
Delta Unsigned
Transmission if the 16 bits input data minimized at
least around the delta value
0x6428
Analogue Input Interrupt Positive
Delta Unsigned
Transmission if the 16 bits input data increased at
least around the delta value