750-880, 750-880/025-000 ETHERNET Programmable Fieldbus Controller
Manual
Version 1.0.1
750-404/000-005
The above Counter Modules have a total of 5 bytes of user data in both the Input
and Output Process Image (4 bytes of counter data and 1 byte of control/ status).
The two counter values are supplied as 16 bits. The following tables illustrate the
Input and Output Process Image, which has a total of 3 words mapped into each
image. Word alignment is applied.
Table 342: Counter Modules 750-404/000-005
Input Process Image
Byte Destination
Offset
High Byte
Low Byte
Description
0 -
S
Status
byte
1
D1
D0
Counter Value of Counter 1
2
D3
D2
Counter Value of Counter 2
Output Process Image
Byte Destination
Offset
High Byte
Low Byte
Description
0 -
C
Control
byte
1
D1
D0
Counter Setting Value of Counter 1
2
D3
D2
Counter Setting Value of Counter 2
750-638,
753-638
The above Counter Modules have a total of 6 bytes of user data in both the Input
and Output Process Image (4 bytes of counter data and 2 bytes of control/status).
The two counter values are supplied as 16 bits. The following tables illustrate the
Input and Output Process Image, which has a total of 4 words mapped into each
image. Word alignment is applied.
Table 343: Counter Modules 750-638, 753-638
Input Process Image
Byte Destination
Offset
High Byte
Low Byte
Description
0
-
S0
Status byte von Counter 1
1
D1
D0
Counter Value von Counter 1
2
-
S1
Status byte von Counter 2
3
D3
D2
Counter Value von Counter 2
Output Process Image
Byte Destination
Offset
High Byte
Low Byte
Description
0
-
C0
Control byte von Counter 1
1
D1
D0
Counter Setting Value von Counter 1
2
-
C1
Control byte von Counter 2
3
D3
D2
Counter Setting Value von Counter 2