WAGO-I/O-SYSTEM 750
Fieldbus Communication 287
750-880, 750-880/025-000 ETHERNET Programmable Fieldbus Controller
Manual
Version 1.0.1
Instance 1 ... 255 (Digital output value 1 up to 255)
Table 236: Discrete Output Point (66
hex
) – Instance 1...255
Attribute
ID
Access
Name
Data type Description
Default
value
1 Get
DopObj_Value
BYTE
Digital
Output
(only Bit 0 valid)
-
Common Services
Table 237: Discrete Output Point (66
hex
) – Common service
Service available
Service
code
Class Instance
Service-Name
Description
0E
hex
Yes
Yes
Get_Attribute_Single Supplies contents of the appropriate
attribute
10
hex
No
Yes
Set_Attribute_Single Modifies an attribute value
12.3.5.18 Discrete Output Point Extended 1 (6A
hex
)
The extension of the "Discrete Output Point" class enables the exchange of data
from a fieldbus node that contains over 255 digital output points (DOPs). The
instance scope of the "Discrete Output Point Extended 1" class covers DOPs from
256 to 510 in the fieldbus node.
Instance 0 (Class Attributes)
Table 238: Discrete Output Point Extended 1 (6A
hex
) – Class
Attribute
ID
Access
Name
Data type Description
Default
value
1
Get
Revision
UINT
Revision of this object
1 (0x0001)
2
Get
Max Instance
UINT
Max. number of instances
-
Instance 256 ... 510 (Digital output value 256 up to 510)
Table 239: Discrete Output Point Extended 1 (6A
hex
) – Instance 256...510
Attribute
ID
Access
Name
Data type Description
Default
value
1 Get
DopObj_Value
BYTE
Digital
Output
(only Bit 0 valid)
-
Common Services
Table 240: Discrete Output Point Extended 1 (6A
hex
) – Common service
Service available
Service
code
Class Instance
Service-Name
Description
0E
hex
Yes
Yes
Get_Attribute_Single Supplies contents of the appropriate
attribute
10
hex
No
Yes
Set_Attribute_Single Modifies an attribute value