392 Appendix
WAGO-I/O-SYSTEM
750
750-880, 750-880/025-000 ETHERNET Programmable Fieldbus Controller
Manual
Version 1.0.1
Pos: 125.6 /Serie 750 (WAGO-I/O-SYSTEM)/Feldbuskommunikation/SNMP (MIB)/WAGO-MIB_Gruppen für 841, 881-Teil 3 @ 7\mod_1275048206942_21.doc @ 57175 @ 333333333333 @ 1
16.2.7 PLC Project Group
The PLC project group contains information about the controller’s PLC program.
Table 431: WAGO MIB – PLC Project Group
Identifier
Entry
Access Description
1.3.6.1.4.1.13576.10.1.30.1
wioProjectId
R
ID of CoDeSys project
1.3.6.1.4.1.13576.10.1.30.2
wioProjectDate
R
Date of CoDeSys project
1.3.6.1.4.1.13576.10.1.30.3
wioProjectName
R
Name of CoDeSys project
1.3.6.1.4.1.13576.10.1.30.4
wioProjectTitle
R
Title of CoDeSys project
1.3.6.1.4.1.13576.10.1.30.5
wioProjectVersion
R
Version of CoDeSys project
1.3.6.1.4.1.13576.10.1.30.6
wioProjectAuthor
R
Author of CoDeSys project
1.3.6.1.4.1.13576.10.1.30.7 wioProjectDescription R
Description
of
CoDeSys
project
1.3.6.1.4.1.13576.10.1.30.8
wioNumberOfIecTasks
R
Number of IEC tasks in the
CoDeSys project
1.3.6.1.4.1.13576.10.1.30.9 wioIecTaskTable
-
1.3.6.1.4.1.13576.10.1.30.9.1 wioIecTaskEntry
-
1.3.6.1.4.1.13576.10.1.30.9.1.1 wioIecTaskId
R
ID of IEC task in the CoDeSys
project
1.3.6.1.4.1.13576.10.1.30.9.1.2 wioIecTaskName
R
Name of IEC task in the
CoDeSys project
1.3.6.1.4.1.13576.10.1.30.9.1.3 wioIecTaskStatus
R
Status of IEC task in the
CoDeSys project
1.3.6.1.4.1.13576.10.1.30.9.1.4 wioIecTaskMode
R
Mode of IEC task in the
CoDeSys project
1.3.6.1.4.1.13576.10.1.30.9.1.5 wioIecTaskPriority
R
Priority of IEC task in the
CoDeSys project
1.3.6.1.4.1.13576.10.1.30.9.1.6 wioIecTaskInterval
R
Interval of cyclic IEC task in
the CoDeSys project
1.3.6.1.4.1.13576.10.1.30.9.1.7 wioIecTaskEvent
R
Event for IEC task in the
CoDeSys project
1.3.6.1.4.1.13576.10.1.30.9.1.8 wioIecTaskCycleCount
R
Count of IEC task in the
CoDeSys project
1.3.6.1.4.1.13576.10.1.30.9.1.9 wioIecTaskCycleTime
R
Last cycle time of IEC task in
the CoDeSys project
1.3.6.1.4.1.13576.10.1.30.9.1.1
0
wioIecTaskCycleTime-
Min
R
Minimal cycle time of IEC task
in the CoDeSys project
1.3.6.1.4.1.13576.10.1.30.9.1.1
1
wioIecTaskCycleTime-
Max
R
Maximal cycle time of IEC
task in the CoDeSys project
1.3.6.1.4.1.13576.10.1.30.9.1.1
2
wioIecTaskCycleTime-
Avg
R
Average cycle time of IE task
in the CoDeSys project