WAGO-I/O-SYSTEM 750
750-880, 750-880/025-000 ETHERNET Programmable Fieldbus Controller
Manual
Version 1.0.1
Pos: 37.1 /Serie 750 (WAGO-I/O-SYSTEM)/Gerätebeschreibung/Bedienelemente/Feldbuskoppler/-controller/Betriebsartenschalter - Überschrift 3, Ansicht und Einleitung (Controller) @ 4\mod_1239106871099_21.doc @ 30280 @ 3 @ 1
4.4.2
Mode Selector Switch
The mode selector switch is located behind the cover flap.
2
1
1
Figure 26: Mode selector switch (closed and open damper of the service port)
Table 15: Mode selector switch
Number
Description
1
Open the damper
2
Operating mode switch
The operating mode switch determines the loading, starting and stopping of the
PLC-application by the controller. This multifunction sliding switch features 3
slide lock positions and a push-button function.
The sliding switch is designed for a number of operations in compliance with
EN61131T2.
NOTICE
Property damages due to set outputs!
Please note that set outputs remain set, when you switch the operating switch
from "RUN" to "STOP" during the current operation. Since the program is no
longer processed, software-related switch offs, i.e. by initiators, are ineffective.
Therefore, program or define all outputs, so that these switch to a safe mode at a
program stop.
Pos: 37.2 /Serie 750 (WAGO-I/O-SYSTEM)/Gerätebeschreibung/Bedienelemente/Feldbuskoppler/-controller/Hinweis: Definieren der Ausgänge für einen Programm-Stopp! (für Betriebsartenschalter mit WBM) @ 4\mod_1240571895008_21.doc @ 31297 @ @ 1
Note
Defining the outputs for a program stop!
In order to switch the outputs to a safe mode at the program stop, define the status
of the outputs at "STOP".
1.
For this, open in the web-based Management System (WBM)
a website via the "PLC" link, on which you can define the function
Process image - Set outputs to zero, if user program is
stopped
.
2.
Now activate this function by placing a check mark in the control box,
then all outputs are set to zero, if
this function is not activated, the outputs remain at the
last current value.
Pos: 37.3 /Serie 750 (WAGO-I/O-SYSTEM)/Gerätebeschreibung/Bedienelemente/Feldbuskoppler/-controller/Betriebsartenschalter - Tabellen (881) @ 8\mod_1278942475895_21.doc @ 59670 @ @ 1