WAGO-I/O-SYSTEM 750
Fieldbus Communication 289
750-880, 750-880/025-000 ETHERNET Programmable Fieldbus Controller
Manual
Version 1.0.1
Instance 766 ... 1020 (Digital Output value 766 up to 1020)
Table 245: Discrete Output Point Extended 3 (72
hex
) – Instance 766...1020
Attribute
ID
Access
Name
Data type Description
Default
value
1 Get
DopObj_Value
BYTE
Digital
Output
(only Bit 0 valid)
-
Common Services
Table 246: Discrete Output Point Extended 2 (6E
hex
) – Common service
Service available
Service
code
Class Instance
Service name
Description
0E
hex
Yes
Yes
Get_Attribute_Single Supplies contents of the appropriate
attribute
10
hex
No
Yes
Set_Attribute_Single Modifies an attribute value
12.3.5.21 Analog Input Point (67
hex
)
This class enables the reading of data of a particular analog input point (AIP). An
analog input point is part of an analog input module.
Instance 0 (Class Attributes)
Table 247: Analog Input Point (67
hex
) – Class
Attribute
ID
Access
Name
Data type Description
Default
value
1
Get
Revision
UINT
Revision of this object
1 (0x0001)
2
Get
Max Instance
UINT
Max. number of instances
-
Instance 1 ... 255 (Analog input 1 up to 255)
Table 248: Analog Input Point (67
hex
) – Instance 1 ... 255
Attribute
ID
Access
Name
Data type Description
Default
value
1 Get
AipObj_Value
ARRAY
of BYTE
Analog Input
-
2 Get
AipObj_Value_
Length
USINT
Length of the output data
AopObj_Value (in byte)
-
Common Services
Table 249: Analog Input Point (67
hex
) – Common service
Service available
Service
code
Class Instance
Service name
Description
0E
hex
Yes
Yes
Get_Attribute_Single Supplies contents of the appropriate
attribute