Programming the PFC using WAGO-I/O-PRO 159
750-880, 750-880/025-000 ETHERNET Programmable Fieldbus Controller
Manual
Version 1.0.1
Pos: 82.71 /Serie 750 (WAGO-I/O-SYSTEM)/In Betrieb nehmen/In WAGO-I/O-PRO programmieren/Applikation via ETHERNET übertragen (881, 880) @ 8\mod_1278940614634_21.doc @ 59647 @ 3 @ 1
9.6.2
Transfer via Fieldbus and ETHERNET
The physical link between the PC and the controller is set up via fieldbus. An
appropriate communication driver is required for data transfer. The driver and its
parameters must be entered in the WAGO-I/O-
PRO
in the dialog window
"Communication parameters".
Note
Controller needs IP address for access!
The controller must have an IP address before it can be accessed. The operating
mode switch, which is located behind the cover of the fieldbus controller next to
the service interface, must be in the center or top position.
1. Start
the
WAGO-I/O-
PRO
software under
Start / Programs / WAGO-I/O-
PRO
or by clicking the program icon on the desktop).
2.
In the menu
Online
select the item
Communication parameters
.
The dialog window "Communication parameters" then appears. The channels of
the currently connected gateway servers are shown on the left side of the dialogue
and the already installed communications drivers are shown below. This window
is empty in its default settings.
3. Click
New
to set up a connection and then specify a name, e.g. TcpIp
connection.
4.
Mark the required TCP/IP driver in the right side of the dialog window to
configure the link between the PC and the controller via ETHERNET.
Use the new driver version "Tcp/Ip" (3S Tcp/Ip driver).
The following standard entries are shown in the center dialog window:
•
IP address:
IP address of your controller
•
Port number:
2455
• Motorolabyteorder: No
•
Debug level:
16#0000
5.
Change any entries as you may require.
6. Confirm
with
OK
.
You have now configured the TCP/IP link with the communication
parameters/drivers.
Pos: 82.72 /Serie 750 (WAGO-I/O-SYSTEM)/In Betrieb nehmen/In WAGO-I/O-PRO programmieren/Online, Einloggen, Bootprojekt erzeugen, Starten der Programmabarbeitung @ 4\mod_1242106439171_21.doc @ 32920 @ @ 1
7. Under
Online
, click the menu item
Login
to log in to the controller
The WAGO-I/O-
PRO
Server is active during online operation. The
communication parameters can not be called up during this time.