WAGO-I/O-SYSTEM 750
Commissioning 121
750-880, 750-880/025-000 ETHERNET Programmable Fieldbus Controller
Manual
Version 1.0.1
Pos: 80.21.1 /Serie 750 (WAGO-I/O-SYSTEM)/In Betrieb nehmen/Feldbusknoten in Betrieb nehmen/IP-Adresse mit einem BootP-Server vergeben (Controller) @ 6\mod_1265022423859_21.doc @ 49093 @ 3 @ 1
8.2.3
Assigning the IP Address with a BootP Server
A BootP server or PLC program can be used to assign a fixed IP address.
When assigning an address using a PLC program, this can be done using the
"Ethernet_Set_Network_Config" function block from the "Ethernet.lib" library
integrated in WAGO-I/O-
PRO
.
Assigning the IP address using a BootP server depends on the respective BootP
program. Handling is described in the respective manual for the program or in the
respective integrated help texts.
Pos: 80.21.2 /Serie 750 (WAGO-I/O-SYSTEM)/In Betrieb nehmen/Feldbusknoten in Betrieb nehmen/Hinweis: Für aktive Software-Konfiguration, Adresswahlschalter auf 0 stellen! (BootP) @ 5\mod_1244020081653_21.doc @ 34753 @ @ 1
Set the address selection switch to 0 for active software configuration!
Set the address selection switch to 0 to disable the DIP switch and to enable the
software configuration via BootP.
Restart the fieldbus node after adjusting the address selection switch to apply the
configuration changes.
Pos: 80.21.3 /Serie 750 (WAGO-I/O-SYSTEM)/In Betrieb nehmen/Feldbusknoten in Betrieb nehmen/Hinweis: IP-Adressvergabe nicht über Router möglich! @ 9\mod_1281680971860_21.doc @ 63546 @ @ 1
IP address assignment is not possible via the router!
The IP address is assigned via patch cable, switches, hubs, or via direct link using
a crossover cable. Addresses can not be allocated via router.
Pos: 80.21.4 /Serie 750 (WAGO-I/O-SYSTEM)/In Betrieb nehmen/Feldbusknoten in Betrieb nehmen/Hinweis: BootP muss im Web-based Management-System aktiviert sein! @ 9\mod_1281681388997_21.doc @ 63558 @ @ 1
BootP must be enabled on the Web pages!
Note that BootP must be enabled on the internal Web pages of the WBM, HTML
page "Port configuration".
BootP is enabled by default when delivered.
Pos: 80.21.5 /Serie 750 (WAGO-I/O-SYSTEM)/In Betrieb nehmen/Feldbusknoten in Betrieb nehmen/Information: IP-Adressvergabe mit BootP-Server auch unter Linux. Beliebiger BootP-Server @ 9\mod_1281681162420_21.doc @ 63552 @ @ 1
Information
Additional Information
Assigning IP addresses using the WAGO-BootP server can be carried out in any
Windows and Linux operating system. Any other BootP servers may also be used,
besides the WAGO-BootP server.
Pos: 80.21.6 /Serie 750 (WAGO-I/O-SYSTEM)/In Betrieb nehmen/Feldbusknoten in Betrieb nehmen/Information: Sie erhalten den „WAGO-BootP-Server 759-315“ kostenlos auf... @ 9\mod_1281681258507_21.doc @ 63555 @ @ 1
Information
More information about the WAGO-BootP-Server
The "WAGO-BootP-Server 759-315" is available free of charge on the CD
"AUTOMATION Tools and Docs" (Art. No.: 0888-0412) or at
AUTOMATION
759-315
WAGO-BootP-Server.
Pos: 80.21.7 /Serie 750 (WAGO-I/O-SYSTEM)/In Betrieb nehmen/Feldbusknoten in Betrieb nehmen/Die Beschreibung umfasst die folgenden Arbeitsschritte: MAC-ID,... (gekürzt für unspez. BootP) @ 6\mod_1265027842746_21.doc @ 49105 @ @ 1