24
System Description
WAGO-I/O-SYSTEM 750
750-880, 750-880/025-000 ETHERNET Programmable Fieldbus Controller
Manual
Version 1.0.1
Pos: 17.13.6 /Serie 750 (WAGO-I/O-SYSTEM)/Systembeschreibung/Versorgung/Systemversorgung @ 3\mod_1232950096265_21.doc @ 26748 @ 3 @ 1
3.6.2
System Supply
Pos: 17.13.7 /Serie 750 (WAGO-I/O-SYSTEM)/Systembeschreibung/Versorgung/Systemversorgung - Anschluss @ 3\mod_1232950096796_21.doc @ 26752 @ 4 @ 1
3.6.2.1
Connection
The WAGO-I/O-SYSTEM 750 requires a 24 V direct current system supply
(-15 % or +20 %). The power supply is provided via the coupler/controller and, if
necessary, in addition via the internal system supply modules (750-613). The
voltage supply is reverse voltage protected.
NOTICE
Do not use an incorrect voltage/frequency!
The use of an incorrect supply voltage or frequency can cause severe damage to
the component.
Pos: 17.13.8 /Serie 750 (WAGO-I/O-SYSTEM)/Systembeschreibung/Versorgung/Systemversorgung - Anschluss - Systemversorgung (St erweiterter ECO) @ 3\mod_1232950104031_21.doc @ 26776 @ @ 1
Figure 4: System supply for standard coupler/controller and extended ECO couplers
Pos: 17.13.9 /Serie 750 (WAGO-I/O-SYSTEM)/Systembeschreibung/Versorgung/Systemversorgung - Anschluss - Die eingespeiste 24 V-Gleichspannung versorgt... @ 3\mod_1232950097328_21.doc @ 26756 @ @ 1
The fed DC 24 V supplies all internal system components, e.g. coupler/controller
electronics, fieldbus interface and bus modules via the internal bus (5 V system
voltage). The 5 V system voltage is electrically connected to the 24 V system
supply.
Pos: 17.13.10 /Serie 750 (WAGO-I/O-SYSTEM)/Systembeschreibung/Versorgung/Systemversorgung - Anschluss - Systemspannung (St erweiterter ECO) @ 3\mod_1232950102359_21.doc @ 26768 @ @ 1