128 Commissioning
WAGO-I/O-SYSTEM
750
750-880, 750-880/025-000 ETHERNET Programmable Fieldbus Controller
Manual
Version 1.0.1
Pos: 80.21.37 /Serie 750 (WAGO-I/O-SYSTEM)/In Betrieb nehmen/Feldbusknoten in Betrieb nehmen/Gründe für eine fehlgeschlagene IP-Adressvergabe (bei BootP) (Controller) @ 4\mod_1239098186078_21.doc @ 30141 @ 4 @ 1
8.2.3.5
Reasons for Failed IP Address Assignment
•
The controller MAC address does not correspond to the entry given in the
"bootstrap.txt" file.
•
The client on whom the BootP server is running is not located in the same
subnet as the controller; i.e., the IP addresses do not match
Example: Client IP: 192.168.0.10 and controller IP: 10.1.254.5
•
Client and/or controller is/are not linked to the ETHERNET
•
Poor signal quality (use switches or hubs)