![WAGO 750-880 Manual Download Page 74](http://html2.mh-extra.com/html/wago/750-880/750-880_manual_3156225074.webp)
74
Connect Devices
WAGO-I/O-SYSTEM 750
750-880, 750-880/025-000 ETHERNET Programmable Fieldbus Controller
Manual
Version 1.0.1
Pos: 64.11 /Serie 750 (WAGO-I/O-SYSTEM)/Anschließen/Leiter an CAGE CLAMP anschließen - Überschrift 2 und Text @ 3\mod_1225448660171_21.doc @ 24928 @ 2 @ 1
6.3
Connecting a conductor to the CAGE CLAMP
®
The WAGO CAGE CLAMP
®
connection is appropriate for solid, stranded and
finely stranded conductors.
Note
Only connect one conductor to each CAGE CLAMP
®
connection!
Only one conductor may be connected to each CAGE CLAMP
®
connection.
Do not connect more than one conductor at one single connection!
If more than one conductor must be routed to one connection, these must be
connected in an up-circuit wiring assembly, for example using WAGO feed-
through terminals.
Exception:
If it is unavoidable to jointly connect 2 conductors, then you must use a ferrule to
join the wires together. The following ferrules can be used:
Length
8
mm
Nominal cross section
max.
1
mm
2
for 2 conductors with 0.5 mm
2
each
WAGO
Product
216-103
or
products
with comparable properties.
1.
To open the CAGE CLAMP
®
insert the actuating tool into the opening
above the connection.
2.
Insert the conductor into the corresponding connection opening.
3.
To close the CAGE CLAMP
®
simply remove the tool - the conductor is
then clamped firmly in place.
Figure 36: Connecting a conductor to a CAGE CLAMP
®
Pos: 65 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.doc @ 21810 @ @ 1