122 Commissioning
WAGO-I/O-SYSTEM
750
750-880, 750-880/025-000 ETHERNET Programmable Fieldbus Controller
Manual
Version 1.0.1
The following steps are included:
•
Note MAC ID
•
Note IP address
•
Assigning the IP address and enable BootP
• Disable
BootP
Pos: 80.21.8 /Serie 750 (WAGO-I/O-SYSTEM)/In Betrieb nehmen/Feldbusknoten in Betrieb nehmen/MAC-ID ermitteln (BootP) Überschrift 4 @ 6\mod_1264500781687_21.doc @ 48740 @ 4 @ 1
8.2.3.1
Note MAC ID
Pos: 80.21.9 /Serie 750 (WAGO-I/O-SYSTEM)/In Betrieb nehmen/Feldbusknoten in Betrieb nehmen/MAC-ID ermitteln - Schritte 1-2 (Controller) @ 5\mod_1244023567062_21.doc @ 34779 @ @ 1
1.
Write down the controller’s MAC address (see label or peel-off strip).
If the fieldbus is already installed, turn off the operating voltage of the
fieldbus controller, then take the fieldbus controller out of the assembly of
your fieldbus node and note the MAC ID of your fieldbus controller.
The MAC ID is applied to the back of the fieldbus controller or on the self-
adhesive peel-off strip on the side of the fieldbus controller.
MAC ID of the fieldbus controller:
0 0 : 3 0 : D E : _ _ : _ _ : _ _
2.
Plug the fieldbus controller into the assembly of the fieldbus node.
Pos: 80.21.10 /Serie 750 (WAGO-I/O-SYSTEM)/In Betrieb nehmen/Feldbusknoten in Betrieb nehmen/Client-PC und Feldbusknoten an Feldbusanschluss anschließen (Aufzählung Fortsetzung) @ 4\mod_1243520482117_21.doc @ 34109 @ @ 1
3.
Use the fieldbus cable to connect the fieldbus connection of your
mechanically and electrically assembled fieldbus node to an open interface
on your computer.
The client PC must be equipped with a network card for this connection.
The controller transfer rate then depends on the network card of your client
PC.
Pos: 80.21.11 /Serie 750 (WAGO-I/O-SYSTEM)/In Betrieb nehmen/Feldbusknoten in Betrieb nehmen/Starten Sie den Client-PC, der die Funktion des Masters und BootP-Servers übernimmt. @ 4\mod_1239087816984_21.doc @ 30067 @ @ 1
4.
Start the client that assumes the function of the master and BootP server.
Pos: 80.21.12 /Serie 750 (WAGO-I/O-SYSTEM)/In Betrieb nehmen/Feldbusknoten in Betrieb nehmen/Schalten Sie die Spannungsversorgung am Controller (DC-24V-Netzteil) ein. @ 4\mod_1239089269406_21.doc @ 30071 @ @ 1
5.
Switch on the power at the controller (DC 24 V power supply unit).
Pos: 80.21.13 /Serie 750 (WAGO-I/O-SYSTEM)/In Betrieb nehmen/Feldbusknoten in Betrieb nehmen/Hochlauf und LEDs (Controller) @ 4\mod_1243521648173_21.doc @ 34301 @ @ 1
After the power is switched on, the controller is initialized. The fieldbus controller
determines the I/O module configuration and creates a process image. During
startup, the I/O LED (red) will flash. After a brief period, the I/O LED lights up
green, indicating that the fieldbus controller is operational.
Pos: 80.21.14 /Serie 750 (WAGO-I/O-SYSTEM)/In Betrieb nehmen/Feldbusknoten in Betrieb nehmen/Hochlauf und LEDs - Fehler allgemein, Hinweis: Signalisierung/Blinkcode-Ausw. @ 4\mod_1243594306433_21.doc @ 34538 @ @ 1
If an error occurs during start-up indicated by the I/O LED flashing red, evaluate
the error code and argument and resolve the error.
Information
More information about LED signaling
The exact description for evaluating the LED signal displayed is available in the
section "Diagnostics", "LED Signaling".
Pos: 80.21.15 /Serie 750 (WAGO-I/O-SYSTEM)/In Betrieb nehmen/Feldbusknoten in Betrieb nehmen/Hochlauf und LEDs - Fehler: keine IP (Controller) @ 6\mod_1264498406795_21.doc @ 48704 @ @ 1
Error codes and error arguments are indicated by the frequency of a LED flash
sequence. For example: Error code 6, followed by error argument 4, is indicated
by the I/O LED after controller start-up with 6 red error code flashes, followed by
four red flashes of the error argument. This indicates that an IP address has not yet
been assigned.