156 Programming the PFC using WAGO-I/O-PRO
WAGO-I/O-SYSTEM 750
750-880, 750-880/025-000 ETHERNET Programmable Fieldbus Controller
Manual
Version 1.0.1
Pos: 82.66 /Serie 750 (WAGO-I/O-SYSTEM)/In Betrieb nehmen/In WAGO-I/O-PRO programmieren/Applikation mittels serieller Schnittstelle übertragen (Einleitung) @ 4\mod_1241516209250_21.doc @ 32380 @ 3 @ 1
9.6.1
Transfer via Serial Service Port
Note
Watch the position of the mode selector switch when accessing the controller!
Prerequisite for the access to the fieldbus controller is that the operating mode
switch of the controller, which is located behind the cover of the fieldbus
controller next to the service interface, is in the center or top position.
Use the WAGO communication cable to set up a physical connection via serial
service port. This cable is included in the scope of supply for the IEC-61131-3
programming tool (Item No.: 759-333), or can be procured as an accessory item
under order no.: 750-920.
Pos: 82.67 /Serie 750 (WAGO-I/O-SYSTEM)/In Betrieb nehmen/Feldbusknoten in Betrieb nehmen/Hinweis: Kommunikationskabel 750-920 nicht unter Spannung stecken! (Controller) @ 6\mod_1264499356321_21.doc @ 48718 @ @ 1
Do not connect 750-920 Communication Cable when energized!
To prevent damage to the communications interface, do not connect or disconnect
750-920 Communication Cable when energized! The fieldbus controller must be
de-energized!
Pos: 82.68 /Serie 750 (WAGO-I/O-SYSTEM)/In Betrieb nehmen/In WAGO-I/O-PRO programmieren/Applikation mittels serieller Service-Schnittstelle übertragen @ 4\mod_1241519721312_21.doc @ 32386 @ @ 1
1.
Check that the controller mode selector switch is set to the center or top
position.
If this is not the case, move the mode selector switch to the center or top
position.
2.
Use the WAGO communication cable to connect a COM port of your PC to
the controller communication port.
A communication driver is required for serial data transfer. This driver and its
parameters must be entered in the WAGO-I/O-
PRO
in the dialog window
"Communication parameters".
3.
Start the WAGO-I/O-
PRO
software
under Start > Programs > WAGO
Software > WAGO-I/O-
PRO
.
4.
In the menu
Online
select the item
Communication parameters
.
The dialog window "Communication parameters" then appears. The channels of
the currently connected gateway servers are shown on the left side of the dialogue
and the already installed communications drivers are shown below. This window
is empty in its default settings.
5. Click
New
to set up a link and then enter a name, such as RS-232
Connection.