114 Commissioning
WAGO-I/O-SYSTEM
750
750-880, 750-880/025-000 ETHERNET Programmable Fieldbus Controller
Manual
Version 1.0.1
Pos: 80.17.1 /Serie 750 (WAGO-I/O-SYSTEM)/In Betrieb nehmen/Feldbusknoten in Betrieb nehmen/IP-Adresse mit dem Adresswahlschalter vergeben - Überschrift 3 @ 5\mod_1243949279644_21.doc @ 34680 @ 3 @ 1
8.2.1
Assigning IP Address via Address Selection Switch
Pos: 80.17.2 /Serie 750 (WAGO-I/O-SYSTEM)/In Betrieb nehmen/Feldbusknoten in Betrieb nehmen/IP-Adresse mit dem Adresswahlschalter vergeben (Controller) - Einleitung @ 5\mod_1243949520694_21.doc @ 34683 @ @ 1
Use the address selection switch to set the host ID, i.e., the last byte of the IP
address , which is entered in the Web-Based Management System on WBM page
“
TCP/IP”
, entry
“DIP switch IP-Adress”,
with values between 1 and 254 binary
coded.
Example:
IP address saved in the fieldbus controller:
192.168.7
Set DIP switch value:
50
(binary coded: 00110010)
Resulting IP address saved in the fieldbus controller:
192.168.7.
50
Note
Host ID 1 - 254 via address selection switch freely adjustable!
Use the address selection switch to set the last byte of the IP address to a value
between 1 and 254. The DIP switch is then enabled and the IP address is
composed of the DIP switch base address stored in the fieldbus controller and the
host ID set on the DIP switch.
The IP address make via the Web-based Management System or WAGO-
ETHERNET-Settings is disabled.
Note
Address selection switch values 0 and 255 are predefined, address selection
switch disabled!
If you use the address selection switch to set the value 0 or 255, the address
selection switch is disabled and the setting configured in the fieldbus controller is
used.
With the value 0, the settings of the Web based Management System or
ETHERNET-Settings apply.
If you set the value 255, the configuration via DHCP is activated.
The base address used consists of the first three bytes of the IP address. This
always depends on the IP address currently saved in the fieldbus controller.
If there is still no static IP address in the fieldbus controller, the default value
192.168.1
defined by the firmware as the base address is used when setting the
DIP switch to 1 - 254.
The address selection switch setting then overwrites the value of the host ID.