124 Commissioning
WAGO-I/O-SYSTEM
750
750-880, 750-880/025-000 ETHERNET Programmable Fieldbus Controller
Manual
Version 1.0.1
8.2.3.3
Assigning the IP address and Enable BootP
1.
Based on the handling, which depends on the BootP program set, assign the
required IP address for your fieldbus node.
2.
Enable the query/response mechanism of the BootP protocol based on the
handling, which depends on the BootP program set.
3.
To apply the new IP address, use a hardware reset to restart your fieldbus
node (interrupt the voltage supply for approx. 2 seconds).
Pos: 80.21.20 /Serie 750 (WAGO-I/O-SYSTEM)/In Betrieb nehmen/Feldbusknoten in Betrieb nehmen/BootP deaktivieren - Überschrift 4 @ 5\mod_1244025692102_21.doc @ 34786 @ 4 @ 1
8.2.3.4
Disabling BootP
Pos: 80.21.21 /Serie 750 (WAGO-I/O-SYSTEM)/In Betrieb nehmen/Feldbusknoten in Betrieb nehmen/Bei aktiviertem BootP-Protokoll erwartet der Controller die permanente Anwesenheit (Controller) @ 4\mod_1239104652546_21.doc @ 30193 @ @ 1
When the BootP protocol is activated the controller expects the BootP server to be
permanently available. If there is no BootP server available after a PowerOn reset,
the network will remain inactive.
Pos: 80.21.22 /Serie 750 (WAGO-I/O-SYSTEM)/In Betrieb nehmen/Feldbusknoten in Betrieb nehmen/Sie müssen das BootP-Protokoll deaktivieren, damit der Controller die IP aus dem RAM in (Controller) @ 4\mod_1239104980734_21.doc @ 30199 @ @ 1
You must then deactivate the BootP protocol so that the controller uses the
configurated IP address from the EEPROM; this does away with the need for the
BootP server to be permanently available.
Pos: 80.21.23 /Serie 750 (WAGO-I/O-SYSTEM)/In Betrieb nehmen/Feldbusknoten in Betrieb nehmen/Hinweis: Für die dauerhafte Adressvergabe, muss BootP deaktiviert werden! (Controller) @ 5\mod_1244028650602_21.doc @ 34812 @ @ 1
BootP must be disabled to assign the address permanently!
To apply the new IP address permanently in the fieldbus controller, BootP must
be disabled.
This prevents the fieldbus coupler from receiving a new BootP request.
Pos: 80.21.24 /Serie 750 (WAGO-I/O-SYSTEM)/In Betrieb nehmen/Feldbusknoten in Betrieb nehmen/Hinweis: Kein Verlust der IP-Adresse bei deaktiviertem BootP-Protokoll (Controller) @ 4\mod_1239105654343_21.doc @ 30205 @ @ 1
The IP address is not lost when the BootP-Protocol is disabled!
If the BootP protocol is deactivated after addresses have been assigned, the stored
IP address is retained, even after an extended loss of power, or when the
controller is removed
Pos: 80.21.25 /Serie 750 (WAGO-I/O-SYSTEM)/In Betrieb nehmen/Feldbusknoten in Betrieb nehmen/Das Deaktivieren von BootP können Sie im WBM vornehmen. (-352, -881, -882) @ 9\mod_1292516140287_21.doc @ 67573 @ @ 1
You can disable in the Web-based Management System.
Pos: 80.21.26 /Serie 750 (WAGO-I/O-SYSTEM)/In Betrieb nehmen/Feldbusknoten in Betrieb nehmen/BootP in dem Web-based Management-System deaktivieren - Zwischenüberschrift @ 5\mod_1244124957364_21.doc @ 34960 @ @ 1
Disable BootP in the Web-based Management System
Pos: 80.21.27 /Serie 750 (WAGO-I/O-SYSTEM)/In Betrieb nehmen/Feldbusknoten in Betrieb nehmen/BootP deaktivieren - Anleitung (Controller) @ 4\mod_1239105878859_21.doc @ 30228 @ @ 1
1. Open
the
Web browser
on your client (such as the Microsoft Internet
Explorer) to have the HTML pages displayed.
2. Enter
the
IP address
for your fieldbus node in the address line of the
browser and press
[Return]
.
A dialog window then appears with a password prompt. This is provided for
secure access and entails three different user groups: admin, guest and user.