196 Diagnostics
WAGO-I/O-SYSTEM
750
750-880, 750-880/025-000 ETHERNET Programmable Fieldbus Controller
Manual
Version 1.0.1
Table 66: Blink code- table for the I/O LED signaling, error code 6
Error code 6: "Fieldbus specific errors"
Error
Argument
Error description
Solution
1
Invalid MACID
1. Turn off the power supply of the node.
2. Exchange
fieldbus
controller.
3. Turn the power supply on again.
2
Ethernet Hardware
initialization error
1. Restart the fieldbus controller by turning the power
supply off and on again.
2. If the error still exists, exchange the fieldbus controller.
3
TCP/IP initialization
error
1. Restart the fieldbus coupler by turning the power
supply off and on again.
2. If the error still exists, exchange the bus coupler.
4
Network configuration
error (no IP Address)
1. Check the settings of BootP server.
5
Application protocol
initialization error
1. Restart the fieldbus coupler by turning the power
supply off and on again.
2. If the error still exists, exchange the bus coupler.
6
Process image is too
large
1. Turn off the power supply of the node.
2. Reduce number of I/O modules
7
Double IP address in
network
1. Change configuration. Use another IP address, which is
not yet present in network.
2. Restart the fieldbus coupler by turning the power
supply off and on again.
8
Error when building
the process image
1. Turn off the power supply of the node.
2. Reduce number of I/O modules
3. Restart the fieldbus coupler by turning the power
supply off and on again.
4. If the error still exists, exchange the bus coupler.
Pos: 88.14 /Serie 750 (WAGO-I/O-SYSTEM)/Diagnose/Feldbuskoppler/-controller/Blinkcode-Tabellen - Fehlercode 6, spezifisches Argument 9) (750-0881, -0880) @ 8\mod_1278680325313_21.doc @ 59485 @ @ 1
9
Error with mapping
between bus modules
and fieldbus
1. Check EA-Config.xml file on the fieldbus controller
Pos: 88.15 /Dokumentation allgemein/Gliederungselemente/------Leerzeile------ @ 3\mod_1224662755687_0.doc @ 24460 @ @ 1
Pos: 88.16 /Serie 750 (WAGO-I/O-SYSTEM)/Diagnose/Feldbuskoppler/-controller/Blinkcode-Tabellen - Fehlercode 7...9 (Fehlercode nicht genutzt) @ 6\mod_1259247106578_21.doc @ 45640 @ @ 1
Table 67: Blink code table for the 'I/O' LED signaling, error code 7…9
Error code 7…9: -not used-