82
Function Description
WAGO-I/O-SYSTEM 750
750-880, 750-880/025-000 ETHERNET Programmable Fieldbus Controller
Manual
Version 1.0.1
Pos: 74 /Alle Serien (Allgemeine Module)/Überschriften für alle Serien/Datenaustausch - Überschrift 2 @ 4\mod_1241431718548_21.doc @ 32202 @ 2 @ 1
7.3
Data Exchange
Pos: 75.1 /Serie 750 (WAGO-I/O-SYSTEM)/Funktionsbeschreibung/Datenaustausch/Datenaustausch - Einleitung Teil 1 (750-841, -871, -881 ) @ 6\mod_1256044434515_21.doc @ 43207 @ @ 1
With the fieldbus controller, data is exchanged via the MODBUS/TCP protocol
and/or the MODBUS/UDP protocol or Ethernet/IP.
Pos: 75.2 /Serie 750 (WAGO-I/O-SYSTEM)/Funktionsbeschreibung/Datenaustausch/Datenaustausch - Einleitung Teil 2 (750-841,-842, -843, -871, -881 ) @ 8\mod_1281078066247_21.doc @ 62560 @ @ 1
MODBUS/TCP works according to the master/slave principle. The master
controller can be a PC or a PLC.
The fieldbus controllers of the WAGO-I/O-SYSTEM 750 are usually slave
devices. Thanks to the programming with IEC 61131-3, however, these
controllers can also assume the master function.
The master requests communication. This request can be directed to certain nodes
by addressing. The nodes receive the request and, depending on the request type,
send a reply to the master.
Pos: 75.3 /Serie 750 (WAGO-I/O-SYSTEM)/Funktionsbeschreibung/Datenaustausch/Datenaustausch - Ein Feldbuscontroller kann eine bestimmte Anzahl gleichzeitiger Verbd. (Controller) @ 6\mod_1256044496578_21.doc @ 43210 @ @ 1
A controller can set up a defined number of simultaneous connections (socket
connections) to other network subscribers:
Pos: 75.4 /Serie 750 (WAGO-I/O-SYSTEM)/Funktionsbeschreibung/Datenaustausch/Datenaustausch - Liste gleichzeitiger Verbindungen (Socket-Verbindungen) (750-841, 881) @ 6\mod_1256044617468_21.doc @ 43216 @ @ 1
•
3 connections for HTTP (to read HTML pages from the controller)
•
15 connections via MODBUS/TCP (to read or write input and output data of
the controller)
•
128 connections for Ethernet/IP
•
5 connections via PFC (available in the PLC function for IEC 61131-3
application programs)
•
2 connections for WAGO-I/O-
PRO
(these connections are reserved for
debugging the application program via ETHERNET. WAGO-I/O-
PRO
needs 2 connections at the same time for the debugging. However, only
one
programming tool can have access to the controller).
•
10 connections for FTP
•
2 connections for SNMP
Pos: 75.5 /Serie 750 (WAGO-I/O-SYSTEM)/Funktionsbeschreibung/Datenaustausch/Datenaustausch - Schnittstellen (Controller) @ 6\mod_1256044722312_21.doc @ 43219 @ @ 1
The maximum number of simultaneous connections can not be exceeded. Existing
connections must first be terminated before new ones can be set up. The
ETHERNET Programmable Fieldbus Controller is essentially equipped with three
interfaces for data exchange:
•
the interface to the fieldbus (Master),
•
the PLC function of the PFC (CPU) and
•
the interface to the I/O modules.