290 Fieldbus Communication
WAGO-I/O-SYSTEM 750
750-880, 750-880/025-000 ETHERNET Programmable Fieldbus Controller
Manual
Version 1.0.1
12.3.5.22 Analog Input Point Extended 1 (6B
hex
)
The extension of the "Analog Input Point" class enables the reading of data from a
fieldbus node that contains over 255 analog outputs (AIPs). The instance scope of
the "Analog Input Point Extended 1" class covers AIPs from 256 to 510 in the
fieldbus node.
Instance 0 (Class Attributes)
Table 250: Analog Input Point Extended 1 (6B
hex
) – Class
Attribute
ID
Access
Name
Data type Description
Default
value
1
Get
Revision
UINT
Revision of this object
1 (0x0001)
2
Get
Max Instance
UINT
Max. number of instances
-
Instance 256 ... 510 (Analog Input value 256 up to 510)
Table 251: Analog Input Point Extended 1 (6B
hex
) – Instance 256 ... 510
Attribute
ID
Access
Name
Data type Description
Default
value
1 Get
AipObj_Value
ARRAY
of BYTE
Analog Input
-
2 Get
AipObj_Value_
Length
USINT
Length of the output data
AopObj_Value (in byte)
-
Common Services
Table 252: Analog Input Point Extended 1 (6B
hex
) – Common service
Service available
Service
code
Class Instance
Service name
Description
0E
hex
Yes
Yes
Get_Attribute_Single Supplies contents of the appropriate
attribute
12.3.5.23 Analog Input Point Extended 2 (6F
hex
)
The extension of the "Analog Input Point" class enables the reading of data from a
fieldbus node that contains over 510 analog outputs (AIPs). The instance scope of
the "Analog Input Point Extended 2" class covers AIPs from 511 to 765 in the
fieldbus node.
Instance 0 (Class Attributes)
Table 253: Analog Input Point Extended 2 (6F
hex
) – Class
Attribute
ID
Access
Name
Data type Description
Default
value
1
Get
Revision
UINT
Revision of this object
1 (0x0001)
2
Get
Max Instance
UINT
Max. number of instances
-
Instance 511 ... 765 (Analog Input 511 up to 765)