352 I/O Modules
WAGO-I/O-SYSTEM 750
750-880, 750-880/025-000 ETHERNET Programmable Fieldbus Controller
Manual
Version 1.0.1
Output Process Image
Byte Destination
Instance
High Byte
Low Byte
Description
- C
Control
byte
D1 D0
n
D3 D2
Counter setting value
And the specialty modules represent 1x6 bytes output data and seize 1 Instance in
Class (0x68).
750-404/000-005
The above Counter Modules have a total of 5 bytes of user data in both the Input
and Output Process Image (4 bytes of counter data and 1 byte of control/ status).
The two counter values are supplied as 16 bits. The following tables illustrate the
Input and Output Process Image, which has a total of 3 words mapped into each
image. Word alignment is applied.
Table 388: Counter Modules 750-404/000-005
Input Process Image
Byte Destination
Instance
High Byte
Low Byte
Description
- S Status
byte
D1
D0
Counter Value of Counter 1
n
D3
D2
Counter Value of Counter 2
The specialty modules represent 2x3 bytes input data and seize 2 Instances in
Class (0x67).
Output Process Image
Byte Destination
Instance
High Byte
Low Byte
Description
- C Control
byte
D1
D0
Counter Setting Value of Counter 1
n
D3
D2
Counter Setting Value of Counter 2
And the specialty modules represent 1x6 bytes output data and seize 1 Instance in
Class (0x68).
750-638,
753-638
The above Counter Modules have a total of 6 bytes of user data in both the Input
and Output Process Image (4 bytes of counter data and 2 bytes of control/status).
The two counter values are supplied as 16 bits. The following tables illustrate the
Input and Output Process Image, which has a total of 4 words mapped into each
image. Word alignment is applied.