Pressure Alarms - The following troubleshooting responses assume that pressure
transducers are properly calibrated and correct setpoints are installed in the configuration
matrix. If corrective action does not alleviate the alarm condition, check setpoints in
configuration file and pressure transducer calibration records.
PT2 (Branch 1 through 4 Delivery Pressure) Alarms
The following are possible branch delivery transducer alarms.
9.6.3 Low Branch Delivery Pressure or Very Low Branch
Delivery Pressure
Probable Cause
Corrective Action
Branch delivery pressure is set below
the low or very low delivery pressure
setpoints.
Process gas supply pressure is not
adequate.
Adjust branch delivery pressure
regulator to achieve the desired
delivery pressure.
Adjust process gas supply pressure
from source. Ensure process gas
manual inlet valve is open.