result. Contact an Versum Materials, Inc.
representative for system verification.
NOTE: Due to the potential hazards listed above, Manual Mode
operation requires a second or higher level security code.
NOTE: Prior to shipment, the GASGUARD Distribution System
panel has been certified to strict cleanliness specifications.
Improper operation of the valves in "Manual Mode" could result
in contamination of the gas panel
NOTE: A pneumatic supply connected to the controller with 85-95
psig (5.9-6.6 barg) of nitrogen must be available to actuate the
valves.
NOTE: Shutdown alarms (indicated by the red SHUTDOWN LED
being lit) will not allow you to access and open valves in manual
mode, therefore making a leak test invalid. If a shutdown alarm is
present, contact an Versum Materials, Inc. representative for system
verification prior to leak testing.
1.
Enter second level (or higher) security code (check with appropriate
Versum Materials, Inc. representative for proper password) as follows:
Touch anywhere on the graphics portion of the screen.
You will see a pop-up window entitled: “Password”
Using the keypad, type in the password.
Press
OK