8.8.1 Net Product
This option allows the operator to display either a gross or net value on any
analog. The gross value will display the normal analog reading with no
adjustment. The net value will display a “net” reading based on the value input by
the operator. If a value other than zero is entered in this window, the “net” value
will be calculated and displayed for this analog. A “net” tag will also appear at the
analog display box. If zero is entered, the gross or unadjusted value will display
with no additional tag.
8.8.2 User Analog Setpoints (User Setpoints)
This option allows the operator to choose an analog input device from a drop
down menu or exit the window. When the operator chooses an analog input
device, the corresponding setpoints will be displayed. The operator has the ability
to select and change any of the setpoints. The User Analog Setpoints window
displays the customer/user defined analog alarm data. The window will display
the alarm number, alarm label, and current alarm setpoint for each user defined
alarm. A total of ten setpoints will exist per analog input. The number of user
setpoints will be equal to ten minus the number of VM setpoints. This window
will allow the operator to enter a new setpoint value for one or more chosen
alarms or exit the window without changes. These setpoints may include one or
more of the following:
Low Branch Del.
High Branch Del.
Low Process Inlet
Low Purge Inlet
8.8.3
Subcycle Parameters