Chapter - 1
MNL000440.doc
Revision 00
09/19/2016
© Versum Materials, Inc. as of the revision and date shown. All rights reserved.
Confidential and Proprietary Data
Page
-
13
•
Safety shower
•
Emergency phones
•
Eye wash
•
Gas leak detection system for gases to be used (ex: MDA)
The gas leak detection system must warn personnel (through visible and
audible alarms located near the gas cabinet) of a hazardous atmosphere.
The gas sensor(s) need to be set up to alarm at the lowest level of hazard of
exposure. Upon activation of an alarm, follow the established shutdown
procedures for your system.
•
Scrubber with a pollution abatement system sized for maximum potential
upset flow of hazardous gas.
•
Adequate ventilation as described in section 3.7.
If you are unsure what personal protective
equipment list to follow for the gases being
used, DO NOT continue. Failure to understand
the hazards and use the proper personal
protective equipment may cause INJURY or
DEATH. Contact Versum Materials, Inc. for the
gas category.