Section 5 - Setup
MM113 - D10/D16 Hot Melt Unit
76
User Inputs and Outputs - Continued
Outputs 1-4
Conditions to Turn Output ON
Disabled None
System Ready
All zones have reached their respective temperature setpoints minus the
System
Ready Temperature Offset AND the Ready Delay Time has elapsed.
System Ready & Pump On All zones have reached their respective temperature setpoints minus the
System
Ready Temperature Offset, the Ready Delay Time has elapsed AND
t
he pump is
ON.
Alarm
High Temperature Alarm OR,
Low Temperature Alarm OR,
RTD Disconnected Alarm OR,
Drive Fault (if equipped) OR,
Filter Alarm (if equipped) OR,
Communication Fault
Power On
Control power is ON
Setback On
Control is in Setback mode
Level 1
Material is below the Level 1 Sensor (if equipped) OR,
Hopper Feeder runs for more than 200 seconds without satisfying Level Sensor (if
equipped)
Level 2
Material is below the Level 2 Sensor (if equipped)
Fault/Stop The
tank
over-temperature thermostat is open OR,
Any zone temperature has increased above the Maximum Temperature Setting
OR,
The High Temperature Alarm or RTD Disconnected Alarm persists for more than
150 seconds
Note: Any of these conditions will cause the control to deactivate the master
control relay
Alarm/Level
High Temp Alarm OR,
Low Temp Alarm OR,
RTD Disconnected Alarm OR,
Drive Fault (if equipped) OR,
Filter Alarm (if equipped) OR,
Communication Fault OR,
Material is below the Low Level Sensor (if equipped) OR,
Hopper Feeder runs for more than 200 seconds without satisfying Level Sensor (if
equipped)
Ready & Level
All zones have reached their respective temperature setpoints minus the System
Ready Temperature Offset, the Ready Delay Time has elapsed AND the material is
below the level 1 sensor.
Pressure Alarm
The pump is ON, the pressure alarm delay has elapsed AND material pressure is
outside of setpoint range.
Summary of Contents for D10
Page 1: ...D10 D16 Hot Melt Unit Manual Number MM113 Revision Date 8 2019 ...
Page 4: ......
Page 10: ...Table of Contents MM113 D10 D16 Hot Melt Unit 10 ...
Page 22: ...Section 2 Safety and Use MM113 D10 D16 Hot Melt Unit 22 ...
Page 24: ...Section 3 Basic Features MM113 D10 D16 Hot Melt Unit 24 ...
Page 38: ...Section 5 Setup MM113 D10 D16 Hot Melt Unit 38 Section 5 Setup Control Panel ...
Page 45: ...MM113 D10 D16 Hot Melt Unit Section 5 Setup 45 Set Language Continued Next Page ...
Page 46: ...Section 5 Setup MM113 D10 D16 Hot Melt Unit 46 Set Language Continued ...
Page 47: ...MM113 D10 D16 Hot Melt Unit Section 5 Setup 47 Set Temperature Units ...
Page 50: ...Section 5 Setup MM113 D10 D16 Hot Melt Unit 50 Hose Valve Temperature Continued ...
Page 57: ...MM113 D10 D16 Hot Melt Unit Section 5 Setup 57 Beacon 2 ...
Page 73: ...MM113 D10 D16 Hot Melt Unit Section 5 Setup 73 Sequential Start Valve ...
Page 84: ...Section 5 Setup MM113 D10 D16 Hot Melt Unit 84 VFD Parameters After 5 18 Before 5 18 ...
Page 98: ...Section 5 Setup MM113 D10 D16 Hot Melt Unit 98 ...
Page 106: ...Section 6 Operation MM113 D10 D16 Hot Melt Unit 106 ...
Page 117: ...MM113 D10 D16 Hot Melt Unit Section 9 Specifications 117 Dimensions D16 ...
Page 118: ...Section 9 Specifications MM113 D10 D16 Hot Melt Unit 118 ...
Page 121: ...MM113 D10 D16 Hot Melt Unit Section 10 Part Number List 121 D10 Unit Continued ...
Page 122: ...Section 10 Part Number List MM113 D10 D16 Hot Melt Unit 122 D10 Unit Continued ...
Page 125: ...MM113 D10 D16 Hot Melt Unit Section 10 Part Number List 125 D10 Base Unit 776xx884 ...
Page 126: ...Section 10 Part Number List MM113 D10 D16 Hot Melt Unit 126 D10 Base Unit 776xx884 Continued ...
Page 150: ...Section 10 Part Number List MM113 D10 D16 Hot Melt Unit 150 D16 Unit Continued ...
Page 151: ...MM113 D10 D16 Hot Melt Unit Section 10 Part Number List 151 D16 Unit Continued ...
Page 154: ...Section 10 Part Number List MM113 D10 D16 Hot Melt Unit 154 D16 Base Unit 776xx885 ...
Page 155: ...MM113 D10 D16 Hot Melt Unit Section 10 Part Number List 155 D16 Base Unit 776xx885 Continued ...
Page 206: ...Section 10 Part Number List MM113 D10 D16 Hot Melt Unit 206 ...
Page 208: ...Section 11 Warranty MM113 D10 D16 Hot Melt Unit 208 ...
Page 210: ...Section 12 Service MM113 D10 D16 Hot Melt Unit 210 ...
Page 214: ...Appendix B Power Requirements MM113 D10 D16 Hot Melt Unit 214 ...
Page 226: ...Appendix D Communication Protocols Modus MM113 D10 D16 Hot Melt Unit 226 ...
Page 269: ......