149
® 2018 Valco Companies, Inc.
The following alarms may be displayed. They are not listed in any particular order. The alarms will be displayed in the
order that they first occur.
Possible Alarm Conditions
#01 Hi/Low Temp CNT 200 VAL 101.9
Temperature exceeded alarm limits.
#01 Air #01 STA#01 CH#02 CNT251 VALFFFE
Invalid temperature reading from air sensor.
#01 24
-
Hour Water Used
-
CNT 2
The total gallons used in the past 24 hours dropped more than the alarm percent drop setting.
#01 ADC5Volt STA#01 ADC:32789 CNT 104
Malfunction in the power supply or analog circuit on the station.
#01
ADC9V
OLT
STA#02
ADC:65531
CNT
20
Malfunction in the power supply or analog circuit on the station.
#01 ADC0Volt STA#03 ADC:32802 CNT 3
Malfunction in the power supply or analog circuit on the station. Possible faulty ground going to the
controller or station.
#01 Erase Error: Sctr:04 CNT 1
Error erasing parameters, history, or errors in the system FLASH memory.
#01 Write Error: Sctr:05 Add:1034 CNT 1
Error writing parameters, history, or errors to the system FLASH memory.
#01 Voltage Low CNT 12
A low
power condition was detected when updating FLASH memory. The 12 VDC supplied by the
control power supply is low. Check input voltage for correct value.
#01 Temp Chg STA01/05 78.1 30.9 CNT 1
An air sensor reading has changed more than 15 degrees Fahrenheit (or about 8.5 degrees Celsius)
from the last reading. The new reading is marked with an “*” (to the left of the affected temp
reading) in current conditions, and is ignored until it reads within 15 degrees of the previous
temperature reading.
#01 Water #2 GPH Exceeds Limit CNT 105
The water flow exceeded the set limit.
#01 Feed
Sensor
#01 ON Time Exceeded
The feed
sensor
run time has exceeded the set limit. This alarm may also show “OFF Time
Exceeded” or “Overload Detected” or “No
-
Load Detected.”
#01 W.Dog CNT
1
The program watch dog timer caused the system to reset.
#01 Comm 13 STA#10 CH#11 CNT145
There is an error communicating with portions of the control or other stations (expansion, modem
or serial interface).
#01 Low Stat Press CNT 140 VAL 0.250
Static
pressure has fallen below the limits you entered. This alarm may also show “High Stat Press”
or “Lo Cyc Stat Press” or “Fan Lo Stat Press.”
#01 Digital Alarm #1 Activated CNT 130
The digital alarm has been activated.
#01 Sidewall Inlet #1 Out of Positio
n
The position sensor is reporting a device position that is different than what the controller expected
based on the device’s Open and Close times.
#01 Position Sta 01/05 C: 11.9 A: 75.0
A position sensor or Whisker Switch is reporting a device position that is different than what the
controller expected. For a Position Sensor, C is the controller calculated position and A is the
position sensor reported position. For a Whisker Switch, C is the controller calculated position and
A is the Whisker Switch reported percentage open.
#01 Position Sensor 2 Bad Reading
The position sensor is reporting bad reading. The reported ohms are out of range of the fully open
to fully closed ohms.
#01 HUMIDITY STA#01 CH#03 CNT 12 VALC17C
A humidity sensor is giving an invalid reading.