100
® 2018 Valco Companies, Inc.
Side Curtain Settings
Input the group numbers of the air sensors you want to use for controlling the curtain. The controller uses Shared
Sensor Technology to average the temperature readings of any sensors you want to use to control any device. This
menu item only appears when the curtain uses a temperature-controlled mode (refer to the Operating Modes:
Curtains and Inlets section).
Z1-S01
Use Sensors: ALL (Avg 74.7)
Input the temperatures at which the controller should open and close the side curtain (when the curtain is in a
temperature-control mode). When the temperature is at or above the Open Temp, the controller opens the curtain
as many inches as you designate (see below). When the temperature is at or below the Close Temp, the controller
closes the curtain as many inches as you designate (see below).
Z1-S01
Open Temp: 80.0 Close Temp: 75.0
This menu item doesn’t appear for curtains set up for tunnel or static control (refer to the Operating
Modes: Curtains and Inlets section).
Open This Distance and Pause
Input the distance the controller should open the curtain before pausing. Then input the Pause time. After the Pause
time, the controller checks the temperature and determines if it should open the curtain more, do nothing, or begin
closing it.
Z1-S01
Open 12” and Pause: 0:02:00
This menu item doesn’t appear for curtains set up for static control (refer to the Operating Modes:
Curtains and Inlets section).
The controller has a minimum motion time of three seconds. For example, if a curtain moves 60 inches in 60 sec
-
onds, 3 inches is the smallest change in opening size that can be made. Opening sizes should be set large enough to
allow a minimum of three seconds movement from one setting to the next.
DEVICE / EQUIPMENT SETTINGS Z1-S01
PRESS ENTER TO VIEW SETTINGS
CONTROL
SETTINGS
Reminder: Curtain Settings are listed under the DEVICE/EQUIPMENT menu.
Use Sensors
Opening and Closing Temp