YO99-0874-DI-002-18
34
Setting of operating frequency (in Mitsubishi FR-E520 series and Mitsubishi FR-F520J series and
Mitsubishi FR-D720 series)
Operating frequency: 60 Hz
Table. 7 Parameter setting: Mitsubishi FR-E520 series
Parameter No.
Parameter
PRC-003A PRC-006A PRC-012A PRC-018A
9
Electronic thermal O/L relay
3.6
9.3
15.1
21.0
19
Base frequency voltage
200
22
Stall prevention operation level
70.0
82.5
84.5
75.0
57
Restart casting time
0
58
Restart cushion time
1
65
Retry selection
0
67
Number of retries at alarm
occurrence
10
68
Retry waiting time
6.0
75
Reset selection/ disconnected PU
detection/ PU stop selection
1
78
Reverse rotation prevention selection
1
79
Operation mode selection
3
80
Motor capacity
0.75
2.2
3.7
5.5
96
Auto-tuning setting/ status
0
146
Frequency setting command
selection
1
250
Stop selection
0
Summary of Contents for PRC-003A
Page 10: ...YO99 0874 DI 002 18 ix Fig 1 Warning Label PRC 003A PRC 006A PRC 012A PRC 018A...
Page 24: ...YO99 0874 DI 002 18 8 2 4 Dimensional drawing Fig 3 PRC 003A Dimensional drawing...
Page 25: ...YO99 0874 DI 002 18 9 Fig 4 PRC 006A Dimensional drawing...
Page 26: ...YO99 0874 DI 002 18 10 Fig 5 PRC 012A Dimensional drawing...
Page 27: ...YO99 0874 DI 002 18 11 Fig 6 PRC 018A Dimensional drawing...
Page 57: ...YO99 0874 DI 002 18 41 Fig 15 PRC 006A Optional attachment figure...
Page 58: ...YO99 0874 DI 002 18 42 Fig 16 PRC 012A Optional attachment figure...
Page 59: ...YO99 0874 DI 002 18 43 Fig 17 PRC 018A Optional attachment figure...
Page 76: ......