YO99-0874-DI-002-18
24
3.5 Water Piping
Connect piping 9.52 mm in diameter or more to the Coolant inlet / outlet using care not to mistake the
ports (Refer to Fig. 3
~
6.)
The water included little impurities (ex. Industrial Water) is recommended for
cooling water.
Depending on the water quality, the inside wall of cooling water tube is covered
with water scale (CaCO
3
etc.) and cooling water flow rate may be decreased.
Cooling water tube is corroded by Chlorine ion (Cl
-
) and cooling water leak may
be caused. In case of using pure water, cooling water leak may be caused by
metal component dissolution, too.
In these cases, the repair service may be for a fee.
[Reference]Standard Water Quality of Industrial Water
Establishment: Japan Industrial Water Association
(1) Be sure to flow the Coolant with the volume indicated on
“
Table. 3
Performance specifications” or more. The pump temperature would rise
up if the water volume becomes less than specified particularly on high
suction pressure operation and cause the pump failure.
(2) You are recommended to put a Flow meter for the Coolant and cause the
interlock so that the Pump stops if the coolant flows less than specified
volume.
(3) When the operation stopped in winter, the water piping and the pump have
a risk of breaking by freeze-up of the water inside. Open the Coolant outlet
during operation stop and storage to discharge the water inside by blowing
in the pneumatic air through the water inlet.
CAUTION
CAUTION
Summary of Contents for PRC-003A
Page 10: ...YO99 0874 DI 002 18 ix Fig 1 Warning Label PRC 003A PRC 006A PRC 012A PRC 018A...
Page 24: ...YO99 0874 DI 002 18 8 2 4 Dimensional drawing Fig 3 PRC 003A Dimensional drawing...
Page 25: ...YO99 0874 DI 002 18 9 Fig 4 PRC 006A Dimensional drawing...
Page 26: ...YO99 0874 DI 002 18 10 Fig 5 PRC 012A Dimensional drawing...
Page 27: ...YO99 0874 DI 002 18 11 Fig 6 PRC 018A Dimensional drawing...
Page 57: ...YO99 0874 DI 002 18 41 Fig 15 PRC 006A Optional attachment figure...
Page 58: ...YO99 0874 DI 002 18 42 Fig 16 PRC 012A Optional attachment figure...
Page 59: ...YO99 0874 DI 002 18 43 Fig 17 PRC 018A Optional attachment figure...
Page 76: ......