F3200/NDU 

 

AS4428.1 

 

INSTALLATION & CONFIGURATION MANUAL

 

 

 
 
 

F3200 PRODUCT MANUAL 

 

Document Number:  LT0255 

 
 

Issue .......... 1.22;       5 July 2016

 

 
 

 
 

--   A P P R O V A L S   -- 

 
  AUSTRALIAN STANDARD AS4428.1 -  ActivFire 

Listing Number ..……………..afp789 

  NEW ZEAL

AND STANDARD NZS4512 2003.……………………………………...VF/632 

  AS/NZS CISPR 22 : 2006 
  AS/NZS 60950-1 : 2015 
 

The F3200 and NDU is manufactured by: 

 

Tyco Fire Protection Products 

17 Mary Muller Drive 

Christchurch 8022 

NEW ZEALAND 

 

Tel: +64 3 389-5096 

Fax: +64 3 389-5938 

 
 

COPYRIGHT (C) 2001, 2004, 2009, 2015, 2016 

 
Information contained in this document is subject to copyright, and shall not be reproduced 
in any form whatsoever, without the written consent of Tyco Fire Protection Products. 
 

 

 Information contained in this document is believed to be accurate and reliable, however 
Tyco Fire Protection Products reserves the right to change the content without prior notice. 
 

Summary of Contents for F3200

Page 1: ...d by Tyco Fire Protection Products 17 Mary Muller Drive Christchurch 8022 NEW ZEALAND Tel 64 3 389 5096 Fax 64 3 389 5938 COPYRIGHT C 2001 2004 2009 2015 2016 Information contained in this document is...

Page 2: ...ing facility allows the user to define detail of the operation of the System is being customised It is possible for the user to program operational features that prevent the unit from meeting statutor...

Page 3: ...ON 3 22 CHAPTER 4 CONFIGURING A FIP 4 1 4 1 GENERAL 4 2 4 2 MODULE CONFIGURATION 4 2 4 3 BATTERY POWER SUPPLY 4 3 4 4 LINKS ON PCB MODULES 4 9 CHAPTER 5 INSTALLATION WIRING 5 1 5 1 INSTALLATION 5 2 5...

Page 4: ...revised and Section 6 2 Gas Flood revised Added section 5 12 section 3 3 5 2 3154 1 04 30 06 04 Preface Pages 5 6 5 15 5 16 5 19 Section 6 2 and Appendix A revised 3322 1 05 01 03 05 Appendix A added...

Page 5: ...Document No LT0255 F3200 NDU AS4428 1 Installation Manual Introduction Issue 1 22 5 July 2016 Page 1 1 CHAPTER 1 INTRODUCTION...

Page 6: ...m Description A description of the structure of the F3200 FIP Chapter 3 Specifications A detailed specification and list of part numbers for the F3200 Chapter 4 Configuring a FIP Information on config...

Page 7: ...LT0256 1 2 2 STANDARDS RELATED This manual makes reference to the following Australian and combined Standards AS1603 4 Automatic Fire Detection and Alarm Systems obsolete Part 1 Control and Indicatin...

Page 8: ...B 2 Nov 2001 Board changed now supports flash B 3 Oct 2002 Minor change B 4 Feb 2003 Circuit correction B 5 April 2003 DFM applied D 6 Jan 09 Logo changed G 11 Oct 14 Add mem SMD EMC PA0873 MAF PSU 3...

Page 9: ...m Signalling Equipment AZC Alarm Zone Circuit or Detection Zone AZF Alarm Zone Facility or Group AS1603 4 terminology AVF Alarm Verification Facility or Check Alarm Bd Board CIE Control Indicating Equ...

Page 10: ...ed Non Battery Backed Voltage WS Warning System Z1 Zone Number 1 program abbreviation Zn1 Zone Number 1 text abbreviation 8RM 8 Relay Module 8ZM 8 Zone Module 1 5 GLOSSARY OF TERMINOLOGY The following...

Page 11: ...Document No LT0255 F3200 NDU AS4428 1 Installation Manual System Description Issue 1 22 5 July 2016 Page 2 1 CHAPTER 2 SYSTEM DESCRIPTION...

Page 12: ...2 1 3 DISPLAYS The primary display of the F3200 is a 2 line by 40 character LCD on which the status messages and prompts are shown The LCD has backlight illumination which is turned on when there is...

Page 13: ...Document No LT0255 F3200 NDU AS4428 1 Installation Manual System Description Issue 1 22 5 July 2016 Page 2 3 FIG 2 1 1 F3200 STANDARD CABINET FRONT VIEW...

Page 14: ...are available The most commonly used versions have small slimline cabinets flush and surface mounting not much larger than the F3200 display keyboard which is fitted on them They receive power from th...

Page 15: ...main panel to provide a common monitoring service connection point with display and control of all facilities on the network The F3200 can be networked in a variety of ways Dual channel RS485 links us...

Page 16: ...battery space The outer door has a large acrylic window to allow viewing of the equipment inside Four versions of FIP are available in this cabinet The FP0781 and FP0783 which cater for up to 64 zone...

Page 17: ...Description Issue 1 22 5 July 2016 Page 2 7 FIG 2 2 1 F3200 STANDARD CABINET WITH CARDFRAME INTERNAL LAYOUT FIG 2 2 2 F3200 SMALL CABINET MAXIMUM CONFIGURATION FP0781 and FP0783 have the Cardframe as...

Page 18: ...r modules 8 Zone Module Mounts on cabinet rear or in Cardframe Includes electronics to I F to 8 Alarm Zone Circuits AZCs 8 open collector auxiliary outputs demountable screw terminals for field wiring...

Page 19: ...Document No LT0255 F3200 NDU AS4428 1 Installation Manual System Description Issue 1 22 5 July 2016 Page 2 9 FIG 2 3 1 SYSTEM STRUCTURE...

Page 20: ...e MAF PSU via two power leads Where more than one is required they are connected in series up to 4 maximum from right to left as viewed from the front on the FIP The 26 way FRC from J13 of the Control...

Page 21: ...Document No LT0255 F3200 NDU AS4428 1 Installation Manual System Specifications Issue 1 22 5 July 2016 Page 3 1 CHAPTER 3 SYSTEM SPECIFICATIONS...

Page 22: ...dframe includes standard EOLRs FP0784 F3200 AS4428 FIP SMALL CABINET 1931 71 8 ZONE Includes Small size cabinet Controller Display with Operator Display Keypad MAF PSU includes 7 relays 3A Battery Cha...

Page 23: ...quipment 4U Display on hinged inner door hinges to right Construction Welded steel Material 1 2mm and 1 6mm mild steel Size Standard 750mm H x 550mm W x 210mm D Iss B cabinet Small 410mm H x 550mm W x...

Page 24: ...Load 2 8Adc for standard PSU Continuous exclude 4 7Adc for 6A PSU only charging Max Warning System 2Adc Current Max Ancillary 2Adc Current on VBF1 Max Ancillary 2Adc allows 3A max LED Display Current...

Page 25: ...is normally energised on and turns off for Battery fail TABLE 3 3 2 BATTERY AND CHARGER MONITORING VOLTAGE SPECIFICATIONS 3 3 3 BATTERY Battery Voltage 24Vdc nominal 2 x 12Vdc Compatible Makes Century...

Page 26: ...tus LEDs off 75mA Current per status LED on 3mA 16 Zone LED Display 0mA 5 5mA LED steady RS485 network interface board PA0773 7 5mA Total electronics and detector max rating 2000mA Notes 1 The base pa...

Page 27: ...tion 25mA 80mA Full cabinet NDU FP0790 Quiescent Alarm Current Consumption Aust mode 1 70mA 165mA Current Consumption NZ mode 2 85mA 150mA 1 Includes controller MAF PSU energised standby relay PA0773...

Page 28: ...3 Low Current 10k 5 400mW resistor 4 Tamper EOL002B active EOL 5 Disabled None Circuit Resistance Capacitance Mode Capacitance Resistance 1 2 4 500nF 50 Ohm max 3 1000nF 800 Ohm max for B2 Alarm 2k Oh...

Page 29: ...de 2 additional current is turned on once the Alarm state is latched refer to Graph 3 4 2 Mode 3 Only Min Typ Max Current into short circuit 34 3mA Current into 800 Ohm note 3 14 2mA 14 8mA 15 3mA Cur...

Page 30: ...2 0 14 0 16 0 18 0 20 0 V o l t s D C Current mA B3 Upper B2 Upper B1 Upper 1 Avail Det lcl Notes 1 The graphs are typical values shown for PCB Iss E3 and later 2 For Issue D2 and earlier subtract 1mA...

Page 31: ...ue E3 and later 2 For Issue D2 and earlier subtract 1mA from each 1 5mA at low voltage 3 The currents are applicable only after Alarm has been latched 4 Current available to the detector prior to Alar...

Page 32: ...cations Page 3 12 5 July 2016 Issue 1 22 A short circuit at the end of an 800 Ohm line will give a B2 Detector Operated alarm A short circuit at the end of a 2k Ohm line will give a B3 programmable co...

Page 33: ...S Battery Termination One pair screw terminals 4sq mm max cable AC Input 31V rms 3 6A rms 2 8mm tab terminals Door Switch 5V 0 5mA Unsupervised 4 Way 1 pcb header J6 MCP 5V 1mA 2k7 EOLR 4 Way 1 pcb he...

Page 34: ...Circuit Resistance 100 Ohm max 3 4 3 CONTROLLER DISPLAY INPUTS Spare DC Input Output 24Vdc nom Demountable screw terminal 4 way J5 Spare Input 22V 10k Ohm pull up resistor Provision for supervision up...

Page 35: ...er Board is used with New Zealand operation only The inputs it provides are Silence Alarms Trial Evac Building Services Restore Lamp Test and External Defect All inputs have closure to zero volts to a...

Page 36: ...angeover contacts Voltage free when unsupervised Termination Demountable screw terminals 1 5sq mm max cable Rating 30V 1Adc inductive 30V 2Adc resistive Note The relays are 2 pole with the second pole...

Page 37: ...emountable screw terminals 1 5sq mm max cable Option 1 Pole voltage free changeover contacts Snip Links Lk2 3 4 Rating 30V 2Adc resistive 30V 1Adc inductive Operation Programmable refer Programming Ma...

Page 38: ...PCB header J10 Serial I O Printer Programmer Port This is same port as Serial Port 0 Form Pseudo RS232 Rx Tx 0V signals only Transient Protection Allows external wiring Transmission Rate 9600 Baud Pr...

Page 39: ...ender Board already has common Normal Defect and Fire status LEDs fitted to it but these may be replicated externally if necessary There are also ancillary defect and fire outputs which are active low...

Page 40: ...Program and view parameters Print and save database Brigade Functions Acknowledge Alarms View alarms Next Prev Reset acknowledged zone in alarm Isolate acknowledged zone in alarm Brigade Test via men...

Page 41: ...9 F4000 RAC EXT INNER DOOR 19 7U mounts up to 4 of 16 LED Display Bd FZ3031 KIT F3200 16 ZONE LED DISPLAY LHS POSITION FP0475 FP F4000 DISPLAY EXTENDER KIT 1901 26 Includes 1 x 16 LED Display Bd 16 zo...

Page 42: ...D and buzzer FP0576 FP F3200 BATTERY BOX FP0584 FP F3200 SMALL EMPTY CABINET FULL WINDOW FP0771 I HUB UPGRADE KIT C W MTG PLATE FP0780 FP F3200 AS4428 FIP NO CARDFRAME 24 ZONE MAX 3A FP0781 FP F3200 A...

Page 43: ...1ST DISPLAY FRC 1 2M Display Bd to Controller for Display Bd in furthest left position included with FZ3031 LT0121 LITERATURE 1931 19 F3200 TECHNICAL MANUAL LT0250 LITERATURE F3200 AS4428 OPERATOR S...

Page 44: ...e B or higher 1931 111 Controller SF0423 SOFTWARE F3200 NDU AS4428 CONTROLLER V5 02 SF0427 SOFTWARE F3200 PAL V1 10 SU0319 SUNDRY MOXA 5 PORT E NET SW 2 MULTI MODE FIBRE SU0320 SUNDRY MOXA 5 PORT E NE...

Page 45: ...Document No LT0255 F3200 NDU AS4428 1 Installation Manual Configuring a FIP Issue 1 22 5 July 2016 Page 4 1 CHAPTER 4 CONFIGURING A FIP...

Page 46: ...he F3200 AS4428 1 Programming Manual LT0256 4 2 MODULE CONFIGURATION The required modules are fitted to the F3200 as described in Section 2 3 2 Note that 8 way modules are connected Bus Out to Bus In...

Page 47: ...c The definition of charging the batteries is supplying enough current to charge them within 24 hours to provide a capacity that will support 5 hours of FIP quiescent load i e with mains off followed...

Page 48: ...Ia for 2 zones in alarm from Section 3 3 5 Include all external loads e g Warning System relays 3 Calculate the 5 hour 0 5 hour battery capacity for the charger requirement as follows Cap 5 hr 5 x Iq...

Page 49: ...for example that the 2 zones in alarm can at most turn on 3 of the 5 module relays plus the External Bell the T GEN 50 Warning System and the Anc 1 load The alarm load for 2 zones in alarm is therefo...

Page 50: ...of the cabinet These very large size batteries may also impede the plugging in and removal of modules fitted to the bottom position of the Cardframe Battery Combinations Large capacity batteries can b...

Page 51: ...Document No LT0255 F3200 NDU AS4428 1 Installation Manual Configuring a FIP Issue 1 22 5 July 2016 Page 4 7 FIG 4 3 2 BATTERY OVERCURRENT PROTECTION FOR LOADS GREATER THAN 3A 20A Fuse 12V 12V...

Page 52: ...ransformer from the AC IN tabs on the MAF PSU Cable tie them safely out of the way if the mains is not connected they will not be live Connect the DC supply ve to the BATTERY terminal and the ve to th...

Page 53: ...ing System Snip all 3 for clean changeover contacts NO COM NC Note that Lk2 Lk4 must remain fitted to provide the required supervision of the Warning System No links are required for Ancillary Relay 1...

Page 54: ...F3200 NDU AS4428 1 Installation Manual Document No LT0255 Configuring a FIP Page 4 10 5 July 2016 Issue 1 22 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 55: ...Document No LT0255 F3200 NDU AS4428 1 Installation Manual Installation Wiring Issue 1 22 5 July 2016 Page 5 1 CHAPTER 5 INSTALLATION WIRING...

Page 56: ...The LCD should be at average eye level and must not be higher than1850 mm or lower than 750 mm above floor level see Fig 5 1 1 5 Clear access and viewing for Fire Fighters and operators 6 At least 1...

Page 57: ...ion Wiring Issue 1 22 5 July 2016 Page 5 3 430 8U Cabinet 415 15U Cabinet 102 8U Cab 150 15U Cab o o o 6 0 o 6 0 280 8U CABINET 450 15U CABINET o o o 6 0 o 6 0 1750 MAX 1220 MIN ALL DIMENSIONS IN MILL...

Page 58: ...B spacers washers and nuts on the inside do not yet fully tighten 6 From the plate rear with the Cardframe firmly against it insert the 3 pop rivets provided into the holes in the Cardframe and rivet...

Page 59: ...unting screw per module should be tightened firmly to earth the module b Modules and FRCs need to be fitted one at a time in the Cardframe It is easier to start from the bottom module and work up c Ca...

Page 60: ...when using the ME0457 4U 80 zone display Fit the FRCs and Minijump link as shown in Fig 5 1 3 It is recommended that the LED Display power leads from the MAF PSU be fitted when more than 8 Display boa...

Page 61: ...4 zones In larger systems with more than approximately 12 LED display boards 192 zones there is an increased possibility of spurious LED operation The problem has been described as leakage from an ind...

Page 62: ...The type format is a 6 lines per inch b 20 characters at 10 CPI or 24 characters at 12 CPI c 2 lines per zone window d 1 line between each zone window To install the zone naming label a Cut out the la...

Page 63: ...d I e no bare wire protruding from the terminal no insulation inside the clamp part of the terminal wire not cut or nicked during stripping wire not soldered wire not doubled back in the demountable t...

Page 64: ...on Board before connecting to the FIP The mains cable connects to the 3 way terminal block mounted to the cabinet rear behind the mains cover a Remove the mains cover with a Pozi screw driver b Shape...

Page 65: ...furthest detector Examples of illegal wiring are shown in Fig 5 3 3 8ZM o o o o o o O CCTn EOL OUT IN OUT IN OUT IN O o o o o o o O FIG 5 3 1 CORRECT AZC DETECTOR WIRING The Tyco SU0600 MCP may be use...

Page 66: ...o o o X X O OUT IN OUT IN OUT IN X L o o o o o o X X X X E o o o o o o O O OUT IN OUT IN OUT IN AZC L o o o o o o O X X o o X X OUT IN X o o X X X X E o o o o o o O O OUT IN OUT IN OUT IN AZC L o o o...

Page 67: ...the cathode of the suppression diode is connected to the positive line Where supervision is required the recommended connection is as shown in Fig 5 4 1 A or B with a return from the furthest door hol...

Page 68: ...witch only Extra Low Voltage ELV signals VNBF o SUPERVISION RETURN SUP o ANCIL NC o ALTERNATIVE 1 COM o 1N4004 0V o SUPPRESSION DOOR HOLDERS DIODE A WITH SUPERVISION OF LOOP POSITIVE WIRING ONLY VNBF...

Page 69: ...less than 400 Ohms a diode of suitable current rating must be added in series with the load at the load as shown below LOAD DIODE DIODE OR DIODE LOAD DIODE 0V 0V FIG 5 4 2 EXAMPLE OF PLANT RELAY WIRI...

Page 70: ...be accommodated by use of a Bell Monitor Board and a separate 6A dc inline fuse See Fig 5 5 5 A relay on an 8 Relay Module can also be used to control and supervise a circuit of evacuation devices Thi...

Page 71: ...Fig 5 5 3 Alternatively the Anc 3 Bells output can be made voltage free remove Links 2 3 4 on the MAF and a spare 8 Zone Input can be used to supervise the Microvac QE90 This arrangement shown in Fig...

Page 72: ...8 o FIG 5 5 1 EXAMPLE OF WIRING WITH 2 SUPERVISED BRANCHES FOR DEVICES WITH NO INTERNAL SERIES DIODE FIG 5 5 2 EXAMPLE OF MULTIPLE MINI GENS WITH 3 BRANCHES OF SPEAKERS F3200 24V Mini Gen PA0895 S S F...

Page 73: ...ssue 1 22 5 July 2016 Page 5 19 FIG 5 5 3 WIRING ANCIL 3 TO MICROVAC QE90 FIG 5 5 4 WIRING ANCIL 3 AND 8ZM INPUT TO MICROVAC QE90 MICROVAC QE90 FIP I P Normally closed Fault relay MICROVAC OR QE90 EOL...

Page 74: ...ING BELL MONITOR BOARD ON ANCIL 3 BELLS RELAY FIGURE 5 5 6 WIRING T GEN 50 TO F3200 BELLS ANC 3 RELAY 2k5 ELD 56k DUAL LINE 50W MAX TOTAL T GEN 50 Master 24V 24V 0V 0V Line ALM SIG NO Fault COM T GEN...

Page 75: ...ltiple co located loads wired in parallel though for multiple co located loads the supervision will not detect a fault if one load becomes disconnected It requires the load or an EOLR to be connected...

Page 76: ...with multiple sets of strobes AVIs This will depend on the type of strobe AVI and the quantity remaining connected The relay should be programmed to operate when either strobe is required and the ope...

Page 77: ...2 0 35mm2 wire to make the connection to the SUP pin Only one Mini Gen or Strobe Driver module is allowed on this arrangement However single or dual speaker strobe branch wiring can be supported The M...

Page 78: ...esistors If there is one Mini Gen Strobe Driver and one branch fit one resistor at the end of this branch and the other across the Mini Gen Strobe Driver and DC terminals If there are two branches or...

Page 79: ...f two branches or 2 Mini Gen Strobe Drivers are used 1 branch each put the EOL at the end of each branch Program the first relay as supervised and the 2nd relay as not with both relays activated by th...

Page 80: ...iring for this Pole 1 is the connector terminals fitted as standard and Pole 2 is the spare set soldered in Note the relay output must be programmed so that supervision of the wiring is disabled when...

Page 81: ...MOS input or monitored 5V 12V or 20V input Refer to Fig 5 7 2 Note that for this to work the 0V supply of the equipment must be connected to the 0V supply of the FIP This may not be desired especially...

Page 82: ...ge 5 28 5 July 2016 Issue 1 22 OCn Cct n EOLR 0V 0V F3200 OTHER EQUIPMENT FIG 5 7 2 EXAMPLE OF INTERFACING TO OTHER EQUIPMENT DIRECT COUPLING VBF OPTOCOUPLER RESISTOR E G 4K7 C Cct n E OCn F3200 OTHER...

Page 83: ...mounting parts and fitting instructions The ASE should be wired directly off the battery via its own fuse Wiring of the ASE FP0740 EOL unit is as per the ASE installation instructions The red wires ar...

Page 84: ...n between both MAF and Non MAF configured RDU s and the FIP NOTES To maintain electrical isolation 1 Lk1 on the MAF PSU Board should be cut for RDUs with their own MAF PSU module 2 Non MAF configured...

Page 85: ...Bd connector J11 Cut Lk1 on MAF PSU O VBF2 O VBF2 O TX O TX RZDU COMMS O 0V O 0V O RX O RX FIP POWERED NON MAF CONFIGURED RDU NON MAF CONFIGURED RDU EXTERNALLY POWERED Ext 24V PSU Cut Lk3 on Remote T...

Page 86: ...upplied Run the 10 way FRC from J7 Network 1 on the Controller to J1 on the RS485 board keeping it tight against the cabinet metalwork by using FRC clamps Run 24V to the J5 terminals on the Controller...

Page 87: ...desired 5 11 2 NZ DISPLAY EXTENDER BOARD The NZ Display Extender board if fitted is positioned at the end of the LED Display Board chain the last LED Display board should have Lk1 removed or connecte...

Page 88: ...igade Test Brigade Isolate These conditions share the same input and when true result in an abnormal system state but defect is not signalled that can be recalled with a system fault recall Lamp Test...

Page 89: ...necessary because the LEDs mounted inside the NDU cabinet do not meet the requirements of NZ4512 with regard to visibility and viewing access An NLDU Network LED Display Unit could also be used to dr...

Page 90: ...mination boards Figure 5 12 1 shows this arrangement Alternatively the PA0769 Termination Board has 3k3 resistors already fitted gives 7mA LED current which is adequate for interior use ii Column Form...

Page 91: ...99 16 Zone Display Board PA0454 Termination Board PA0483 Termination Board PA0483 26 Way FRC Termination Board PA0483 16 Zone Display Board PA0454 26 Way FRC 6 way cable Miscellaneous Inputs Wiring to...

Page 92: ...6 way cable Miscellaneous Inputs NDU Cabinet External Mimic Display Cabinet Wiring to individual common LEDs with series resistors and optional index lamp 24V Note 16 Zone display boards are not norma...

Page 93: ...ludes an RS485 board which is mounted on standoffs in the right hand side cabinet wall It also includes installation instructions looms and other hardware Where the panels have more than 10 zones or 2...

Page 94: ...to be fitted in each panel These provide 2 fibre optic paths that should be arranged in a ring Each fibre path can be changed to using a copper pair by fitting an Ethernet Extender at each end of the...

Page 95: ...Document No LT0255 F3200 NDU AS4428 1 Installation Manual Applications Issue 1 22 5 July 2016 Page 6 1 CHAPTER 6 APPLICATIONS...

Page 96: ...Programmable zones allows non latching non MAF non FF non Bells Ancillaries status only i e Fan Control Panel output relays can switch AZCs and the corresponding zones can be programmed as non fire zo...

Page 97: ...xt and for options A and C following the word off could be programmed as zone text so that Manual Alarm is on and off Alarm is off For option B the text LCD would display fault for off Zone text would...

Page 98: ...lemented by soldering the extra resistor and wires onto the unused contact of the rotary switch on the PCB In all cases auto is zone normal OFF o AUTO o o 6V8 ON o AZC OR 2K7 560E A WITH A ROTARY SWIT...

Page 99: ...1 3 configuration is similar but in the output logic off is ZnF and on is ZnA For two AZC inputs OFF o 2K7 AZC 1 AUTO o o ON o 2K7 AZC 2 FIG 6 1 4 FAN CONTROL WITH TWO AZCs ROTARY OR CENTRE OFF SWITC...

Page 100: ...AZC 6V8 RUN OR 560E A B FIG 6 1 5 EXAMPLE OF FAN RUN FAULT WIRING TO AZC 6 1 3 RELAYS The exact number of relays per fan control and the logic required depends on the particular building and air condi...

Page 101: ...he AS1668 LEDs and so it doesn t matter if the AS1668 panel requires more open collectors than circuits VBF 3K3 RUN OC1 Red 3K3 FAULT OC2 Yellow 3K3 STOP OC3 Green A THREE OPEN COLLECTOR O PS PER FAN...

Page 102: ...NCTION WIRE COLOUR 24V J19 24V J33 24V RED GRN J20 GRN J34 UNUSED YEL J21 YEL J35 YELLOW FAULT LED O C YELLOW RED J22 RED J36 RED RUN O C BLUE SW J23 SW J37 SWITCH I P BROWN 0VA J24 0VA J38 0VA SWITCH...

Page 103: ...0113 module but involve selective snipping out of components as detailed on the instructions 1945 19 3 AS1668 CONTROL MODULE CIRCUIT 3 1945 19 4 AS1668 CONTROL MODULE CIRCUIT 4 The original AS1668 kit...

Page 104: ...Ss and AVI warning signs available LCS includes Gas Start Gas Inhibit switches status LEDs AVIs include selectable Alert and Evac tones and can be ordered with lettering such as FIRE ALARM DO NOT ENTE...

Page 105: ...Document No LT0255 F3200 NDU AS4428 1 Installation Manual Applications Issue 1 22 5 July 2016 Page 6 11 FIGURE 6 2 1 GAS RELEASE LOGIC DIAGRAM...

Page 106: ...1st stage sign FIRE ALARM Relay 2 Evac O P 2nd stage sign EVACUATE and DO NOT ENTER Relay 3 Gas Release Solenoid Relay 4 System Inoperative sign Isolate Guard Relay see note 2 Timer T1 S30 0 V1 30 Sec...

Page 107: ...ndby else an ancillary relay or a module relay each rated at 2Adc resistive on a separate 8RM to Gas Release For multiple zones a Module Relay Guard relay can be common for 2 Gas zones or Brigade Rela...

Page 108: ...ming ve voltage so that the supervision can detect that the element has been fired See Figure 6 2 2 a Multiple actuators may be connected in series on one circuit but each must have the red wire to th...

Page 109: ...ce with regulator at furthest point b Multiple devices with current regulator at furthest point EOL c Multiple devices with limiting resistor not recommended method FIGURE 6 2 2 A C CONNECTING CV98 AC...

Page 110: ...aisy chained AVIs IN T operates the top LEDs for which the default tone is Alert IN B operates the bottom LEDs for which the default tone is Evac COM is the power supply common in a 3 wire arrangement...

Page 111: ...th Evac IN B IN T Top FIRE ALARM Top Alert IN T IN B Bottom DO NOT ENTER Both Evac IN B IN T Top DO NOT ENTER Top Evac IN T IN B 3 Bottom XXXX GAS DISCHARGE Both Evac 1 IN B IN T 3 Both XXXX SYSTEM IN...

Page 112: ...2a RL2b can be two separate relays driven together LK3 LK6 fitted FIGURE 6 2 3 AVI MK2 WIRING USING 2 WIRES For FIRE ALARM DO NOT ENTER FIRE ALARM EVACUATE AREA RL1 Stage 1 S Supervised EOL 2k7 RL2 St...

Page 113: ...the ME0065 ME0069 gas control door to a common 0V and switched 24V outputs refer Section 6 2 6 All signs should be configured for flashing illumination as that attracts attention and saves power Note...

Page 114: ...aution when working on gas extinguishing systems disconnect the actuator or remove it from the gas release valve Identify the thick black wire that runs from the Relay 1 2 and 4 NO terminals to 0V on...

Page 115: ...Z3A Z4A Relay 2 Z4A V1 V1 Z1A Z2A Z5A Z3A Where Z1 Detection circuit 1 Z2 Detection circuit 2 Z3 Gas Start LGCS Z4 Gas Released Pressure Switch Z5 Gas Inhibited Program the panel as otherwise describe...

Page 116: ...F3200 NDU AS4428 1 Installation Manual Document No LT0255 Applications Page 6 22 5 July 2016 Issue 1 22 FIG 6 2 6 LOCAL GAS CONTROL STATION FRONT VIEW...

Page 117: ...t Alarm ZnM 2 Loop Resistance of 150 Ohm to 800 Ohm For this resistance range the AZC has to be programmed into Low Current Mode and voltage band B1 should be programmed as Fault or Alarm but must not...

Page 118: ...s of the MAF Brigade relays as appropriate Note that the EOL required depends on the mode programmed for the AZC FAULT NC o o o EOL ALARM AZC1 o NO ISOLATE NC o o o EOL STANDBY AZC2 o NC FIG 6 3 1 EXA...

Page 119: ...ved IS Intrinsically Safe detectors and bases with IS isolators or Zener barriers and approved cabling 2 Use approved detectors with explosion proof housings and compatible cabling These are not discu...

Page 120: ...red see Section 6 4 3 3 3 Use a 4 terminal isolating repeater where all detectors generate a short circuit alarm condition see Section 6 4 3 4 For these the total capacitance and inductance of the det...

Page 121: ...Ex 251 or KFD0 CS Ex 2 51P is effectively two KHD0 ICS Ex 151 or KFD0 CS Ex 1 51P isolators respectively in one package 2 The resistance quoted in Table 6 4 2 for fire wire is per wire thus the circu...

Page 122: ...as shown As the open collector is standard with an 8ZM it is the cheapest alternative Programming Limitations All detector types require the circuit to be programmed for Mode 1 Std with voltage band B...

Page 123: ...2 2km R 32 M 0 02km C 0 02km C 100 100 2nF 2nF 20 0 5km C 0 5km C 50nF 50nF 10 0 9km C 0 9km C 90nF 90nF 1 1 26km C 1 26km C 126nF 126nF FLAME MS302Ex M300 40 M 3km R 2 2km R 40 M 0 7km C 0 7km C 100...

Page 124: ...odule that can be added to a panel to make it compatible with a wider range of detectors in particular when using IS repeaters It can support up to 2mA of quiescent detector current and normally uses...

Page 125: ...C 0 37km R 17 17 17 17 HEAT FW105 1 3km TOT 1 3km TOT 100 TOT 100 TOT 130nF 130nF 40 M 3km R 2 2km R 40 M 1 3km C 1 3km C HEAT T54B 100 100 130nF 130nF HEAT T56B Z500N 40 M 3km R 2 2km R 40 M 1 3km C...

Page 126: ...on and what the maximum value is 5 The M after a detector quantity indicates the maximum quantity allowed per circuit 6 The maximum detector quantity permitted is calculated using a maximum circuit cu...

Page 127: ...5mm 1 00mm 0 75mm HEAT HEAT HEAT FW105 T54B T56B Z500N 40 M 40 M NOTE 2 3 68 TOT 2km R 68 TOT 2km R 100 NOTE 2 3 68 TOT 1 5km R 68 1 5km R 68 40 M 40 M 1 3km TOT 130nF 1 3km C 130nF 1 3km C 130nF 1 3k...

Page 128: ...rminals The Vigilant Contact Conversion Module part number PA0443 may be used as a conversion interface between the contacts and an F3200 AZC This small encapsulated module has three wires protruding...

Page 129: ...added to a panel to make it compatible with a wider range of detectors The ZAU401 supports up to 2mA of quiescent detector current thus only 5 S231i or S231f detectors can be used on each ZAU401 It o...

Page 130: ...F3200 NDU AS4428 1 Installation Manual Document No LT0255 Applications Page 6 36 5 July 2016 Issue 1 22 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 131: ...Document No LT0255 F3200 NDU AS4428 1 Installation Manual Alignment Adjustment Placing into Operation Issue 1 22 5 July 2016 Page 7 1 CHAPTER 7 ALIGNMENT ADJUSTMENT PLACING INTO OPERATION...

Page 132: ...5 9V Adjust until the 15 9V reference on TP15 is 15 90Vdc R94 Fault Threshold Snip as required to set Fault Threshold to R105 nominal 19 03V MAF PSU PT1 Battery Charger Voltage Should the battery char...

Page 133: ...k that the 8 way modules and if required the 16 Zone LED Displays are fitted and connected correctly See Sections 2 3 2 4 2 and 5 11 3 Check that any additional overcurrent protection device is fitted...

Page 134: ...Check that the green MAINS ON LED indicator is on The Controller performs tests on its memory electronics and the LCD STEP 6 Check that the LCD has good visibility The LCD displays the FIP PCB config...

Page 135: ...___ B Cabinet undamaged Paint OK C Door aligned correctly D Window undamaged and fitted correctly E MCP fitted and undamaged F Cabinet Door locks firmly operates microswitch G Lock 003 Type two keys s...

Page 136: ...Fuse Blown LED off F VRECT at DC IN tab 40 42Vdc G Charger Voltage 27 25 27 4V warm 27 5 27 75V cold 4 OPERATION A LEDs flash aligned with windows MAINS ON LED on B Buzzer pulses with microswitch ope...

Page 137: ...wn and with different cables to isolate the problem Shift reg driver fault This message indicates a problem with the software driver for the shift register bus Clock crystal timebase check fail This m...

Page 138: ...F3200 NDU AS4428 1 Installation Manual Document No LT0255 Alignment Adjustment Placing into Operation Page 7 8 5 July 2016 Issue 1 22 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 139: ...4 40 1 MU614 CO FIRE DETECTOR 5B or M614 40 T614A or T614A Mk2 HEAT DETECTOR TYPE A 5B or M614 40 2 T614B or T614B Mk2 HEAT DETECTOR TYPE B 5B or M614 40 2 T614C or T614C Mk2 HEAT DETECTOR TYPE C 5B o...

Page 140: ...H F3200 FIP MAX NO TYPE DESCRIPTION BASE 4mA IS B111B BEAM SMOKE DETECTOR NOTE 7 40 0 B21B BEAM SMOKE DETECTOR 1 0 C23B IONISATION SMOKE DETECTOR Z23 40 0 C23Bex x IONISATION SMOKE DETECTOR IS Z23 40...

Page 141: ...or 100 40 2 4098 9621EA Type D Heat Detector 100 40 2 4098 9601EA Photoelectric Smoke Detector 100 40 4098 9603EA Ionisation Smoke Detector 100 40 4098 9612 Fixed Temperature Heat Detector 100 40 4098...

Page 142: ...ons 6 Detectors indicated by an normally use an incandescent lamp which will have a low intensity when used in mode 1 The lamp can be replaced with an LED kit 7 The B111B beam and V41B V42B V44B flame...

Page 143: ...icators directly so that the alarm voltage is out of the B2 range approx 3V 13V the circuit will have to be programmed accordingly In some cases constraints are also applied to zone programming For ex...

Page 144: ...ed as Alarm as well as B2 Hard Contact Detectors Hard contact detectors that are not fitted to an electronic base may also be connected directly across the circuit Program the detector type as appropr...

Page 145: ...R614 PHOTOELECTRIC SMOKE DETECTOR B2 MR614T HIGH PERFORMANCE OPTICAL SMOKE DETECTOR B2 MU614 CARBON MONOXIDE DETECTOR B2 T614A HEAT DETECTOR TYPE A B2 T614B HEAT DETECTOR TYPE B B2 T614C HEAT DETECTOR...

Page 146: ...DES 1 2 TYPE DESCRIPTION MODE 1 MODE 2 4098 9618EA HEAT DETECTOR TYPE A B2 4098 9619EA HEAT DETECTOR TYPE B B2 4098 9621EA HEAT DETECTOR TYPE D B2 4098 9603EA IONISATION DETECTOR B2 4098 9601EA PHOTOE...

Page 147: ...W81B HEAT DETECTOR CABLE FW68 FW105 IS B1 B2 P24B PHOTOELECTRIC SMOKE DETECTOR B2 B2 P29B PHOTOELECTRIC SMOKE DETECTOR B2 B2 P61B PHOTOELECTRIC SMOKE DETECTOR REV J B2 P76B PHOTOELECTRIC SMOKE DETECTO...

Page 148: ...or both modes 1 and 2 will give B2 voltage just less than 12V For non latching operation the zone must be programmed as non latching 3 The C23B and C23BEx old types of detectors may have a nominal 6V...