System termination diagrams
BAS-APG001-EN
37
Tracer MP581 to FACP wiring
The wiring between the Tracer MP581 and the FACP is non-supervised
and power limited. In addition:
•
Tracer MP581 and FACP must be in the same room.
•
Wiring between the Tracer MP581 and FACP must be in conduit.
•
Wiring distance cannot exceed 20 ft.
•
Wire must be #18 AWG.
The number of wires needed between the Tracer MP581(s) and the FACP
is determined by the total number of zones in the fire alarm system.
Multiple Tracer MP581 panels may be required to monitor and control
the FACP.
Table 10 gives wiring information for a typical Tracer MP581 that
communicates to an FACP.
Figure 15 on page 38 shows the details for wiring a Tracer MP581 to an
FACP.
Table 10. Wiring for a typical Tracer MP581 that communicates to an
FACP
Cables
per Tracer
MP581
Type of
wiring
Function
1–36
22 Vdc
Two binary input wires per FSCS switch
(up to 36 per Tracer MP581)
1
22 Vdc
Common
Summary of Contents for Engineered Smoke Control System
Page 1: ...BAS APG001 EN Applications Guide Engineered Smoke Control System for TRACER SUMMIT ...
Page 2: ......
Page 6: ......
Page 12: ...Contents vi BAS APG001 EN ...
Page 30: ...Chapter 1 Smoke control overview 18 BAS APG001 EN ...
Page 48: ...Chapter 3 Installation diagrams 36 BAS APG001 EN Figure 14 Tracer MP581 to FSCS wiring ...
Page 50: ...Chapter 3 Installation diagrams 38 BAS APG001 EN Figure 15 Tracer MP581 to FACP wiring ...
Page 57: ...Wiring high voltage ac power BAS APG001 EN 45 Figure 19 AC wiring ...
Page 59: ...EMI RFI considerations BAS APG001 EN 47 Figure 20 Checking the earth ground ...
Page 75: ...EMI RFI considerations BAS APG001 EN 63 Figure 31 Checking the earth ground ...
Page 96: ...Chapter 5 Installing the Tracer MP581 programmable controller 84 BAS APG001 EN ...
Page 110: ...Chapter 6 Installing the EX2 expansion module 98 BAS APG001 EN ...
Page 123: ...End process verification BAS APG001 EN 111 Figure 61 ast actuator fail checkb 3 13 06 ...
Page 132: ...Chapter 7 Programming 120 BAS APG001 EN ...
Page 151: ...Understanding bindings BAS APG001 EN 139 Figure 79 Mixed subnet node and group bindings ...
Page 152: ...Chapter 8 Network variable bindings 140 BAS APG001 EN ...
Page 154: ...Appendix A References 142 BAS APG001 EN ...
Page 155: ......