Chapter 2 Pre-installation considerations
24
BAS-APG001-EN
The smoke control system controls fans and positions dedicated and
nondedicated dampers, both in the smoke control zones and at the air-
handling systems. It may also position dampers or air modulation devices
such as variable-air-volume (VAV) boxes serving the smoke control zones.
Equipment associated with the smoke control system includes: dampers,
fans, verification of operation equipment, and the Tracer™ MP581
programmable controller.
For VAV-based systems, there must be some form of duct pressure relief
on each floor or in each smoke control zone. In smoke control mode, all
return and supply dampers will be set to 100% open. If the VAV dampers
are closed when this occurs, the duct pressure may be enough to damage
duct work. To avoid this possibility, duct pressure relief dampers, either
DDC or mechanically controlled, should be installed in the ductwork for
each smoke control zone.
It should be noted that careful sizing of smoke control supply air damper
and relief damper is necessary to use smoke purge and protect dampers.
In contrast to a VAV system, it is not necessary to provide separate duct
pressure relief in constant volume as this is a form of dedicated smoke
purge with supply and return/exhaust dampers already open. Supply
dampers should be sized such that any one damper can spill an adequate
amount of air.
Outdoor air, return air, relief, and exhaust dampers
A nondedicated comfort control system controls outdoor air, return air,
relief, and exhaust dampers. In normal operation, the return damper
operates in opposition to the outdoor air damper. However, during smoke
control system activation, all three dampers may be closed
simultaneously to isolate the air-handling system for smoke control
operations.
An elevator shaft damper, located at the top of a hoistway, relieves
pressure generated during elevator operation. Since elevator shaft
dampers are usually open, the natural stack effect of the building will
tend to distribute smoke through the building via the elevator shafts.
Some codes require a key-operated switch at the main floor lobby to close
the elevator shaft damper. With local approval, this switch can be located
at the FSCS.
Smoke dampers
A smoke damper is located in any duct that penetrates a smoke zone
perimeter. Smoke dampers that are listed by Underwriters Laboratories
(UL) are subject to more stringent leakage tests than are standard
control dampers. The listing usually includes the control actuator as part
of the smoke damper assembly, but does not include the end switches.
IMPORTANT
Smoke dampers must have a Underwriters Laboratories (UL) listing for
smoke control applications (UL 555S).
Summary of Contents for Engineered Smoke Control System
Page 1: ...BAS APG001 EN Applications Guide Engineered Smoke Control System for TRACER SUMMIT ...
Page 2: ......
Page 6: ......
Page 12: ...Contents vi BAS APG001 EN ...
Page 30: ...Chapter 1 Smoke control overview 18 BAS APG001 EN ...
Page 48: ...Chapter 3 Installation diagrams 36 BAS APG001 EN Figure 14 Tracer MP581 to FSCS wiring ...
Page 50: ...Chapter 3 Installation diagrams 38 BAS APG001 EN Figure 15 Tracer MP581 to FACP wiring ...
Page 57: ...Wiring high voltage ac power BAS APG001 EN 45 Figure 19 AC wiring ...
Page 59: ...EMI RFI considerations BAS APG001 EN 47 Figure 20 Checking the earth ground ...
Page 75: ...EMI RFI considerations BAS APG001 EN 63 Figure 31 Checking the earth ground ...
Page 96: ...Chapter 5 Installing the Tracer MP581 programmable controller 84 BAS APG001 EN ...
Page 110: ...Chapter 6 Installing the EX2 expansion module 98 BAS APG001 EN ...
Page 123: ...End process verification BAS APG001 EN 111 Figure 61 ast actuator fail checkb 3 13 06 ...
Page 132: ...Chapter 7 Programming 120 BAS APG001 EN ...
Page 151: ...Understanding bindings BAS APG001 EN 139 Figure 79 Mixed subnet node and group bindings ...
Page 152: ...Chapter 8 Network variable bindings 140 BAS APG001 EN ...
Page 154: ...Appendix A References 142 BAS APG001 EN ...
Page 155: ......