Chapter 7 Programming
118
BAS-APG001-EN
Nondedicated smoke purge
(UL-864: 3.21.h)
The term
nondedicated
refers to a system that provides the building’s
HVAC functioning under normal conditions and a smoke control objective
during a fire alarm condition.
The main concern when designing a nondedicated system is for
programming to ensure that, once a smoke alarm or FSCP override
occurs, any component of the smoke control system is controlled solely by
automatic smoke control or manual override commands. For details
regarding priority, see Table 28 on page 101.
Figure 70 shows an example of programming for a nondedicated system
to implement the priorities in Table 28. In this figure, the smoke control
dampers for Floor 1 are controlled. The actuator position, either Open or
Closed, will default to whatever the HVAC system commands. There are
two states that will turn control over to either automatic smoke control or
FSCP overrides:
•
If the broadcast general smoke alarm is TRUE, or
•
If the FSCP override switch is set to either Open or Closed.
Figure 70. Implementing priorities for a nondedicated system:
Controlling damper actuators
Summary of Contents for Engineered Smoke Control System
Page 1: ...BAS APG001 EN Applications Guide Engineered Smoke Control System for TRACER SUMMIT ...
Page 2: ......
Page 6: ......
Page 12: ...Contents vi BAS APG001 EN ...
Page 30: ...Chapter 1 Smoke control overview 18 BAS APG001 EN ...
Page 48: ...Chapter 3 Installation diagrams 36 BAS APG001 EN Figure 14 Tracer MP581 to FSCS wiring ...
Page 50: ...Chapter 3 Installation diagrams 38 BAS APG001 EN Figure 15 Tracer MP581 to FACP wiring ...
Page 57: ...Wiring high voltage ac power BAS APG001 EN 45 Figure 19 AC wiring ...
Page 59: ...EMI RFI considerations BAS APG001 EN 47 Figure 20 Checking the earth ground ...
Page 75: ...EMI RFI considerations BAS APG001 EN 63 Figure 31 Checking the earth ground ...
Page 96: ...Chapter 5 Installing the Tracer MP581 programmable controller 84 BAS APG001 EN ...
Page 110: ...Chapter 6 Installing the EX2 expansion module 98 BAS APG001 EN ...
Page 123: ...End process verification BAS APG001 EN 111 Figure 61 ast actuator fail checkb 3 13 06 ...
Page 132: ...Chapter 7 Programming 120 BAS APG001 EN ...
Page 151: ...Understanding bindings BAS APG001 EN 139 Figure 79 Mixed subnet node and group bindings ...
Page 152: ...Chapter 8 Network variable bindings 140 BAS APG001 EN ...
Page 154: ...Appendix A References 142 BAS APG001 EN ...
Page 155: ......