Chapter 8 Network variable bindings
124
BAS-APG001-EN
In Table 31, the term
multi-vibrator
is used to indicate a network
variable whose state is changed regularly. The receiver expects this value
to change state within a certain interval. If it does not, a communication
fault is generated. The term
comm. status
is used to indicate a network
variable whose state is dependent on that particular MP581’s EX2 and
BMTX communication status. If either are down, a communication fault
is generated.
Table 31. Watchdog communication alarm custom bindings
Function
Originator
Network
variable
Destination
Communication check from hub
multi-vibrator
MP580-2
nvoSwitch36
Mechanical system/nviSwitch38
nvoSwitch36
MP580-3/nviSwitch38
nvoSwitch36
MP580-4/nviSwitch38
Communication check to hub
multi-vibrator
Mechanical system
nvoSwitch38
MP580-2/nviSwitch34
Communication check to hub:
FSCP unit multi-vibrator
MP580-3
nvoSwitch38
MP580-2/nviSwitch35
MP580-4
nvoSwitch38
MP580-2/nviSwitch36
BMTX/EX2 communication
check
Mechanical system
nvoSwitch39
MP580-2/nviSwitch37
BMTX/EX2 communication
check to FSCP unit comm. status
MP580-3
nvoSwitch39
MP580-2/nviSwitch38
MP580-4
nvoSwitch39
MP580-2/nviSwitch39
Summary of Contents for Engineered Smoke Control System
Page 1: ...BAS APG001 EN Applications Guide Engineered Smoke Control System for TRACER SUMMIT ...
Page 2: ......
Page 6: ......
Page 12: ...Contents vi BAS APG001 EN ...
Page 30: ...Chapter 1 Smoke control overview 18 BAS APG001 EN ...
Page 48: ...Chapter 3 Installation diagrams 36 BAS APG001 EN Figure 14 Tracer MP581 to FSCS wiring ...
Page 50: ...Chapter 3 Installation diagrams 38 BAS APG001 EN Figure 15 Tracer MP581 to FACP wiring ...
Page 57: ...Wiring high voltage ac power BAS APG001 EN 45 Figure 19 AC wiring ...
Page 59: ...EMI RFI considerations BAS APG001 EN 47 Figure 20 Checking the earth ground ...
Page 75: ...EMI RFI considerations BAS APG001 EN 63 Figure 31 Checking the earth ground ...
Page 96: ...Chapter 5 Installing the Tracer MP581 programmable controller 84 BAS APG001 EN ...
Page 110: ...Chapter 6 Installing the EX2 expansion module 98 BAS APG001 EN ...
Page 123: ...End process verification BAS APG001 EN 111 Figure 61 ast actuator fail checkb 3 13 06 ...
Page 132: ...Chapter 7 Programming 120 BAS APG001 EN ...
Page 151: ...Understanding bindings BAS APG001 EN 139 Figure 79 Mixed subnet node and group bindings ...
Page 152: ...Chapter 8 Network variable bindings 140 BAS APG001 EN ...
Page 154: ...Appendix A References 142 BAS APG001 EN ...
Page 155: ......