Chapter 8 Network variable bindings
122
BAS-APG001-EN
Tracer MP580/581 bindings
This section discusses which network variables will be necessary to
achieve UUKL time performance requirements. Only “generic” network
variables, which are neither Space Comfort Controller (SCC) or Discharge
Air Controller (DAC), are necessary. Use of generic variables does not
affect either BCU auto-bound network variables or SCC or DAC based
network variables.
Receiving data
A network variable input (nvi)
receives
data from other devices on the
LonTalk network. The generic network variable inputs, nviSwitch and
nviPercent, that are commonly used in Tracer MP580/581 bindings are
shown in Table 29.
Sending data
A network variable output (nvo)
send
s data to other devices on the Lon-
Talk network. The generic network variable outputs, nvoSwitch and nvo-
Percent, that are commonly used in Tracer MP580/581 bindings are
shown in Table 30.
Heartbeated network variables
All necessary information can be sent using nvoSwitch (SNVT_switch)
and nvoPercent (SNVT_lev_percent), which are “heartbeated” variables.
All necessary information can be received using nviSwitch
(SNVT_switch) and nviPercent (SNVT_lev_percent). Heartbeated
variables are a means of indicating freshness of information and/or
quality of the communication link. For more information regarding
heartbeating, see “Understanding bindings” on page 130.
Table 29. Tracer MP580/581 generic network variable inputs
Variable name
SNVT
Data type
Description
nviSwitch01 …
nviSwitch40
SNVT_switch
Binary
Bind to these 40 network variable inputs to communi-
cate binary values to the device.
nviPercent01 …
nviPercent20
SNVT_lev_percent
Analog
Bind to these 20 network variable inputs to communi-
cate levels in percent to the device. The valid range is
from –163.84% to 163.83% with a resolution of 0.005%.
Table 30. Tracer MP580/581 generic network variable outputs
Variable name
SNVT
Data type
Description
nvoSwitch01 …
nvoSwitch40
SNVT_switch
Binary
These 40 network variable outputs communicate binary
values to other devices.
nvoPercent01 …
nvoPercent20
SNVT_lev_percent
Analog
These 20 network variable outputs communicate levels
in percent to other devices. The valid range is from –
163.84% to 163.83% with a resolution of 0.005%.
Summary of Contents for Engineered Smoke Control System
Page 1: ...BAS APG001 EN Applications Guide Engineered Smoke Control System for TRACER SUMMIT ...
Page 2: ......
Page 6: ......
Page 12: ...Contents vi BAS APG001 EN ...
Page 30: ...Chapter 1 Smoke control overview 18 BAS APG001 EN ...
Page 48: ...Chapter 3 Installation diagrams 36 BAS APG001 EN Figure 14 Tracer MP581 to FSCS wiring ...
Page 50: ...Chapter 3 Installation diagrams 38 BAS APG001 EN Figure 15 Tracer MP581 to FACP wiring ...
Page 57: ...Wiring high voltage ac power BAS APG001 EN 45 Figure 19 AC wiring ...
Page 59: ...EMI RFI considerations BAS APG001 EN 47 Figure 20 Checking the earth ground ...
Page 75: ...EMI RFI considerations BAS APG001 EN 63 Figure 31 Checking the earth ground ...
Page 96: ...Chapter 5 Installing the Tracer MP581 programmable controller 84 BAS APG001 EN ...
Page 110: ...Chapter 6 Installing the EX2 expansion module 98 BAS APG001 EN ...
Page 123: ...End process verification BAS APG001 EN 111 Figure 61 ast actuator fail checkb 3 13 06 ...
Page 132: ...Chapter 7 Programming 120 BAS APG001 EN ...
Page 151: ...Understanding bindings BAS APG001 EN 139 Figure 79 Mixed subnet node and group bindings ...
Page 152: ...Chapter 8 Network variable bindings 140 BAS APG001 EN ...
Page 154: ...Appendix A References 142 BAS APG001 EN ...
Page 155: ......