Figure 59 illustrates a basic actuator failure routine. Some changes are
necessary when automatic self-testing is added to the program. The
different ways of controlling an actuator have different means of resetting
a failure. The failure reset is automatic if a failure is discovered during an
automatic smoke alarm response or manual override from the smoke
control panel. The failure indication is only maintained while there is a
failure. On the other hand, the triggering of a system self-test, either
scheduled or manual, will reset any failures discovered during a previous
system self test. Figure 60 and Figure 61 on page 111 show the changes
necessary to any dedicated system failure test routine. In either case, the
connected BCU should be programmed to store the actuator failure in the
alarm log.
Binary variable 21 goes true for a minimum of 10 seconds whenever a
system self-test is triggered (see Figure 56 on page 106). This will reset
any stored failures from a previous system self-test.
Figure 60. ast actuator fail checka 3-13-06
Summary of Contents for Engineered Smoke Control System
Page 1: ...BAS APG001 EN Applications Guide Engineered Smoke Control System for TRACER SUMMIT ...
Page 2: ......
Page 6: ......
Page 12: ...Contents vi BAS APG001 EN ...
Page 30: ...Chapter 1 Smoke control overview 18 BAS APG001 EN ...
Page 48: ...Chapter 3 Installation diagrams 36 BAS APG001 EN Figure 14 Tracer MP581 to FSCS wiring ...
Page 50: ...Chapter 3 Installation diagrams 38 BAS APG001 EN Figure 15 Tracer MP581 to FACP wiring ...
Page 57: ...Wiring high voltage ac power BAS APG001 EN 45 Figure 19 AC wiring ...
Page 59: ...EMI RFI considerations BAS APG001 EN 47 Figure 20 Checking the earth ground ...
Page 75: ...EMI RFI considerations BAS APG001 EN 63 Figure 31 Checking the earth ground ...
Page 96: ...Chapter 5 Installing the Tracer MP581 programmable controller 84 BAS APG001 EN ...
Page 110: ...Chapter 6 Installing the EX2 expansion module 98 BAS APG001 EN ...
Page 123: ...End process verification BAS APG001 EN 111 Figure 61 ast actuator fail checkb 3 13 06 ...
Page 132: ...Chapter 7 Programming 120 BAS APG001 EN ...
Page 151: ...Understanding bindings BAS APG001 EN 139 Figure 79 Mixed subnet node and group bindings ...
Page 152: ...Chapter 8 Network variable bindings 140 BAS APG001 EN ...
Page 154: ...Appendix A References 142 BAS APG001 EN ...
Page 155: ......