Custom bindings
BAS-APG001-EN
123
Custom bindings
A distinction is made between FSCP and mechanical system control in
this section. While smoke control panel processing is predictable,
mechanical system processing (actuators, feedback validation) is
unknown. It is limited to approximately five smoke control zones based
on the UUKL-approved smoke control panel. Because the number and
application of each MP581 and EX2 modules is unknown, the mechanical
system will be represented as a “cloud.”
The recommended smoke control system design is to have one MP580/581
assigned as the “communication clearing house” or hub. It may be
necessary to use two or more hubs, one for panel control and another
hub(s) for the mechanical system. This design will simplify the binding
creation process and makes the system more scalable. For more
information regarding the limitations placed on custom binding and
recommendations regarding custom binding design, see “Understanding
bindings” on page 130.
The bindings and variables shown in Table 31–Table 37 were those used
in the tested UUKL system to send information between MP580s. The
system programmer can use whatever bindings and variables are
necessary.
UUKL binding list (watchdog communication)
“Trouble signals and their restoration to normal shall be annunciated
within 200 seconds of the occurrence of the adverse condition, fault, or the
restoration to normal.” (UL-864: 49.2.b)
As there is no built in means of verifying inter-MP581 communication
status, a programmed solution must be used. While a network variable
“heartbeat” can be used to verify status, it can take up to 300 seconds for
a communication failure to be noticed. This solution would fail to meet
the requirement given in previous paragraph. The tested solution is
based on a “watchdog” style where a continuously changing network
variable triggers a timer every time it changes state. As long as the timer
never expires, it is assumed that the two devices are communicating. In
this fashion, a communication failure can be annunciated within 60
seconds.
Table 31 on page 124 shows an example of a custom binding list. One
group binding binds MP580-2, which is the hub, to all other MP581s (for
an explanation of group bindings, see “Understanding bindings” on
page 130). The “watchdog” signal sent to the group is used by each
receiver to confirm communications from the hub unit. The hub unit is
able to validate communications from each of other MP581s using their
individual “watchdog” signals. These bindings are point-to-point based.
There may be two hubs in the system, one used with the FSCP and other
within the mechanical system. The need for a second hub will be driven
by the size of the mechanical system involved. Figure 71 on page 125
illustrates watchdog communication between MP581s in a hub-based
system.
Summary of Contents for Engineered Smoke Control System
Page 1: ...BAS APG001 EN Applications Guide Engineered Smoke Control System for TRACER SUMMIT ...
Page 2: ......
Page 6: ......
Page 12: ...Contents vi BAS APG001 EN ...
Page 30: ...Chapter 1 Smoke control overview 18 BAS APG001 EN ...
Page 48: ...Chapter 3 Installation diagrams 36 BAS APG001 EN Figure 14 Tracer MP581 to FSCS wiring ...
Page 50: ...Chapter 3 Installation diagrams 38 BAS APG001 EN Figure 15 Tracer MP581 to FACP wiring ...
Page 57: ...Wiring high voltage ac power BAS APG001 EN 45 Figure 19 AC wiring ...
Page 59: ...EMI RFI considerations BAS APG001 EN 47 Figure 20 Checking the earth ground ...
Page 75: ...EMI RFI considerations BAS APG001 EN 63 Figure 31 Checking the earth ground ...
Page 96: ...Chapter 5 Installing the Tracer MP581 programmable controller 84 BAS APG001 EN ...
Page 110: ...Chapter 6 Installing the EX2 expansion module 98 BAS APG001 EN ...
Page 123: ...End process verification BAS APG001 EN 111 Figure 61 ast actuator fail checkb 3 13 06 ...
Page 132: ...Chapter 7 Programming 120 BAS APG001 EN ...
Page 151: ...Understanding bindings BAS APG001 EN 139 Figure 79 Mixed subnet node and group bindings ...
Page 152: ...Chapter 8 Network variable bindings 140 BAS APG001 EN ...
Page 154: ...Appendix A References 142 BAS APG001 EN ...
Page 155: ......