CODE No. (DN)
01
Item
Table 1. Setting data (CODE No. table (example))
Setting data
Factory-set value
Filter sign lighting time
Depending on Type
02
Filter pollution level
0000: standard
03
Central control address
0099: Not determined
06
Heating suction temperature shift
Depending on Type
0F
Cooling only
0000: Heat pump
10
Type
Depending on model type
11
Indoor unit capacity
Depending on capacity type
12
System address
0099: Not determined
13
Indoor unit address
0099: Not determined
14
Group address
0099: Not determined
19
Louver type (wind direction adjustment)
Depending on Type.
28
Power failure automatic recovery
0000: None
5d
High ceiling SW
0000: Standard
F0
Swing mode
0001: Standard
F1
Louver fixing position (Flap No. 1)
0000: Not fixed
F2
Louver fixing position (Flap No. 2)
0000: Not fixed
F3
Louver fixing position (Flap No. 3)
0000: Not fixed
F4
Louver fixing position (Flap No. 4)
0000: Not fixed
77
Dual set point
0000: Unavailable
b3
Soft cooling
0001: Available
Fd
Priority operation mode (FS unit)
0000: Heating
FE
FS unit address
0099: Unfixed
b5
Occupancy sensor: Provided/None
0000: None
b7
Occupancy sensor: Operation at absent time
0000: Stand by
31
Ventilation fan (standalone)
0000: Not available
32
Sensor SW (Selection of static pressure)
0000: Body sensor
60
Timer setting (wired remote controller)
0000: Available
d0
Remote controller operation save function
0001: Enable
F6
Presence of Application control kit
0000: None
2b
Thermostat output SW (T10
)
0000: Thermostat ON
1E
Temperature range of cooling/heating
automatic SW control point
0003: 3 deg (Ts ±1.5)
b6
Occupancy sensor: Enable/Invalid
(Judgment time of absence)
0002: Enable (60 min.)
Setting data
000
1
000
4
00
06
00
07
00
08
00
16
Type
Table 2. Type: Code No.10
Model name
4
-way cassette
Concealed Duct Standard
Concealed Duct High static pressure
Ceiling
High Wall
Concealed Duct High static pressure
fresh air intake
MMU-UP**
*
*H
P
MM
D
-UP*
*
**
B
H
P
MM
D
-UP**
*
*H
P
MM
C
-UP**
*
*H
P
MM
K
-UP*
*
**H
P
MM
D
-UP*
*
**
HFP
Setting data
0000*
0044
0041
0001
0003
0005
0007
Model
Table 3. Indoor unit capacity: Code No.11
Invalid
003 type
005 type
007 type
009 type
012 type
015 type
Setting data
0009
0011
0012
0015
0017
0018
Model
018 type
024 type
027 type
036 type
048 type
056 type
00
18
Console
MM
L
-UP*
*
**
NHP
001
3
0
30
type
00
23
00
24
00
25
0
96
type
112
type
128
type
00
21
0
72
type
- 167 -
Summary of Contents for MMC-UP0151HP-E
Page 41: ...2 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 41 ...
Page 42: ...MMC UP0241HP E TR MMC UP0271HP E TR 6 4 12 7 42 ...
Page 43: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 43 ...
Page 58: ...3 WIRING DIAGRAMS 3 1 4 way cassette type MMU UP HP E TR 58 ...
Page 59: ...3 2 Ceiling type MMC UP HP E TR 59 ...
Page 60: ...3 3 Concealed Duct Standard type MMD UP BHP E TR 60 ...
Page 61: ...3 4 Concealed Duct High Static Pressure type MMD UP HP E TR 61 ...
Page 62: ...Concealed Duct High Static Pressure type MMD UP HP E TR 62 ...
Page 63: ...3 5 Concealed Duct High Static Pressure fresh air intake type MMD UP HFP E TR 63 ...
Page 65: ...3 7 High wall type MMK UP HP E TR 65 ...
Page 249: ...MMU UP0361HP E TR MMU UP0481HP E TR MMU UP0561HP E TR 268 267 213 214 249 ...
Page 252: ...12 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 025 024 252 ...
Page 254: ...MMC UP0241HP E TR MMC UP0271HP E TR 029 028 254 ...
Page 256: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 051 028 027 256 ...
Page 261: ...MMD UP0151BHP E TR MMD UP0181BHP E TR 240 239 238 233 235 261 ...
Page 263: ...MMD UP0241BHP E TR MMD UP0271BHP E TR MMD UP0301BHP E TR 240 239 238 233 235 263 ...
Page 265: ...MMD UP0361BHP E TR MMD UP0481BHP E TR MMD UP0561BHP E TR 240 239 238 233 235 265 ...