No.
Part to be replaced
Work procedure
Remarks
⑪
TA sensor
1. Detachment
1) Remove the electric parts box cover and the bottom
plate (suction side). (see the 1.of No,
①
, 1.of No.
⑥
)
2) Disconnect the TA sensor connector from the indoor
control board.
3) Remove the TA sensor by pinching the lock for the TA
sensor holder from the outside of the electric parts box
and pushing it to inside of the electric parts box.
2. Attachment
1) Secure the TA sensor to the holder, and attach it to the
electric parts box.
2) Re-connect the TA sensor connector to the indoor
control board in the same way as before replacement.
3) Attach the electronic parts box cover and the bottom
plate. (see the 2. of No,
①
, 2. of No.
⑥
)
TA sensor
CN104 (Yellow)
Electric parts box
TA sensor holder
⑫
Reactor
1. Detachment
1) Remove the electric parts box cover and the bottom
plate (suction side). (see the 1.of No,
①
, 1.of No.
⑥
)
2) Remove the Fastons for the reactor leads (CN511,
CN510) from the fan control board.
3) Remove the screws A (3 pcs) for the reactor cover,
and slide in the arrow direction to remove.
4) Remove the screws B (4 pcs) to secure the reactor,
and remove the reactor from the reactor cover.
2. Attachment
1) Mount the reactor to the reactor cover.
(Screw B (4 pcs))
2) Reinstall the reactor cover in the same way as before
replacement.
(Screw A (3 pcs))
3) Pull the leads for the reactor into the electric parts box,
and connect to the fan control board in the same way
as before replacement.
CN511
CN510
Screw A
Reactor
Screw B
Reactor assembly
Reactor
cover
- 221 -
Summary of Contents for MMC-UP0151HP-E
Page 41: ...2 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 41 ...
Page 42: ...MMC UP0241HP E TR MMC UP0271HP E TR 6 4 12 7 42 ...
Page 43: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 43 ...
Page 58: ...3 WIRING DIAGRAMS 3 1 4 way cassette type MMU UP HP E TR 58 ...
Page 59: ...3 2 Ceiling type MMC UP HP E TR 59 ...
Page 60: ...3 3 Concealed Duct Standard type MMD UP BHP E TR 60 ...
Page 61: ...3 4 Concealed Duct High Static Pressure type MMD UP HP E TR 61 ...
Page 62: ...Concealed Duct High Static Pressure type MMD UP HP E TR 62 ...
Page 63: ...3 5 Concealed Duct High Static Pressure fresh air intake type MMD UP HFP E TR 63 ...
Page 65: ...3 7 High wall type MMK UP HP E TR 65 ...
Page 249: ...MMU UP0361HP E TR MMU UP0481HP E TR MMU UP0561HP E TR 268 267 213 214 249 ...
Page 252: ...12 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 025 024 252 ...
Page 254: ...MMC UP0241HP E TR MMC UP0271HP E TR 029 028 254 ...
Page 256: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 051 028 027 256 ...
Page 261: ...MMD UP0151BHP E TR MMD UP0181BHP E TR 240 239 238 233 235 261 ...
Page 263: ...MMD UP0241BHP E TR MMD UP0271BHP E TR MMD UP0301BHP E TR 240 239 238 233 235 263 ...
Page 265: ...MMD UP0361BHP E TR MMD UP0481BHP E TR MMD UP0561BHP E TR 240 239 238 233 235 265 ...